Solid State Relays
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: January 10, 2014
Rated
voltage |
Rated current | Must operate voltage | Must release voltage | Input voltage | ||
---|---|---|---|---|---|---|
AC | DC | % of rated voltage | ||||
50 Hz | 60 Hz | |||||
12 VDC | --- | --- | 15 mA | 10.8 V | 1 V | ±10% |
24 VDC | --- | --- | 12 mA | 21.6 V | ||
24 VAC/DC | 20 mA | 21 mA | 11 mA | 21.6 V | ||
48 VAC/DC | 10 mA | 11 mA | 6 mA | 43.2 V | ||
110 VAC | 7.5 mA | 8.2 mA | --- | 99 V | ||
230 VAC | 7.3 mA | 8.6 mA | --- | 207 V |
Rated
voltage |
Rated current | Must operate voltage | Must release voltage | Input voltage | ||
---|---|---|---|---|---|---|
AC | DC | % of rated voltage | ||||
50 Hz | 60 Hz | |||||
12 VDC | --- | --- | 15 mA | 10.8 V | 1 V | ±10% |
24 VDC | --- | --- | 12 mA | 21.6 V | ||
24 VAC/DC | 20 mA | 21 mA | 11 mA | 21.6 V | ||
48 VAC/DC | 10 mA | 11 mA | 6 mA | 43.2 V | ||
110 VAC | 7.5 mA | 8.2 mA | --- | 99 V | ||
230 VAC | 7.3 mA | 8.6 mA | --- | 207 V |
Rated
voltage |
Rated current | Must operate voltage | Must release voltage | Input voltage | ||
---|---|---|---|---|---|---|
AC | DC | % of rated voltage | ||||
50 Hz | 60 Hz | |||||
12 VDC | --- | --- | 8 mA | 10.8 V | 1 V | ±10% |
24 VDC | --- | --- | 4.5 mA | 21.6 V | ||
24 VAC/DC | 10.7 mA | 11.1 mA | 4.3 mA | 21.6 V | ||
48 VAC/DC | 9.6 mA | 10.2 mA | 6 mA | 43.2 V | ||
110 VAC | 6.8 mA | 7.5 mA | --- | 99 V | ||
230 VAC | 6.8 mA | 8.1 mA | --- | 207 V |
Item | G3RV-SL700/500-A(L) | G3RV-SL700/500-D |
---|---|---|
Rated load voltage | AC 100 to 240 V (50/60 Hz) | DC 5 to 24 V |
Load voltage range | AC 75 to 264 V (50/60 Hz) | DC 3 to 26.4 V |
Load current | 0.1 to 2 A (Ta=40°C) | 100 µA to 3 A (Ta=40°C) |
Inrush current | 30 A (60 Hz/1 cycle) | 30 A (60 Hz/1 cycle) |
Permissible I2t; Joule Integral
(Reference value) |
15 A 2 s | 9 A 2 s |
Application load capacity | 400 W (Output voltage: AC 200 V) | 72 W (Output voltage: DC 24 V) |
Item | G3RV-SL700/500-A | G3RV-SL700/500-AL | G3RV-SL700/500-D |
---|---|---|---|
Operate time | 1/2 of load power source
cycle + 1 ms max. |
1 ms max. | 6 ms max. |
Release time | 40 ms max. | 20 ms max. | 60 ms max. |
Output ON voltage drop | 1.6 V rms max. | 0.9 V max. | |
Leakage current | 5 mA max. (at 200 VAC 50/60 Hz) | 10 µA max. (at 24VDC) | |
Insulation resistance | 100 MΩ min. (at 500 VDC) | ||
Dielectric strength | AC2500V 50/60 Hz for 1 min between input and output | ||
Vibration resistance | Malfunction: 10 to 55 to 10 Hz, 0.7-mm single amplitude | ||
Shock resistance | 300m/s2 | ||
Ambient temperature | Storage: -30 to +100°C (with no icing or condensation)
Operating: -30 to +55°C (with no icing or condensation) |
||
Ambient humidity | 45 to 85%RH | ||
Weight | Approx. 38 g | ||
Pollution degree | 2 | ||
Degree of protection according
to IEC 60529 |
IP20 | ||
Rated Impulse Withstand Voltage | 4.0 kV/III | ||
Load category | LC-A | DC-12 | |
Overload Current Profile | 1.5Ie 1.1Ue
5 s ON, 10 s OFF, 10 cycles |
||
Rated insulation Voltage | 240 V |
Model | Input ratings | Contact ratings |
---|---|---|
G3RV-SL700/500-D Series | 12, 24 VDC
24, 48 VAC/DC 110, 230 VAC |
24 VDC 3 A (Resistive Load) at 25°C |
G3RV-SL700/500-A(L) Series | 12, 24 VDC
24, 48 VAC/DC 110, 230 VAC |
Input ratings | Contact ratings |
---|---|
12, 24 VDC
24, 48 VAC/DC 110, 230 VAC |
24 VDC 3 A (Resistive Load) |
12, 24 VDC
24, 48 VAC/DC 110, 230 VAC |
Input | Rated voltage | 30 VAC/VDC max. |
---|---|---|
Current capacity | 0.5 A per channel | |
2.0 A total current, power supply terminal | ||
Characteristics | Ambient temperature | Operating: 0 to 55°C
Storage: - 20 to 85°C |
Overvoltage category | III | |
Pollution degree | 2 |
Max current
(EN60947-7-1 section 8.3.3/1991) |
32 A |
---|---|
Max. Voltage | 400 VAC |
Max. Voltage
when cutting Cross-bar without using separation plate or end-bracket |
250 VAC |
last update: January 10, 2014