Mechatronic Analog Timer
last update: June 10, 2014
Operating mode | ON-delay |
---|---|
Screw tightening torque | 0.98 Nm (10 kgf) max. |
Input type | Voltage input |
Output type | Relay: DPDT |
Mounting method | Flush/Panel mounting, no restriction on mounting angle. |
Approved standards | UL 508, CSA C22.2 No. 14 Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100 Output category according to IEC60947-5-1 |
Model |
Full scale on dial |
Set time unit | |||||
---|---|---|---|---|---|---|---|
s | 10 s | min | 10 min | h (hour) | 10 h (hour) | ||
H3AM-[][][]-A | 3 | --- | 0.5 to 30 s | 0.05 to 3 min | 0.5 to 30 min | 0.05 to 3 h | 0.5 to 30 h |
H3AM-[][][]-B | 6 | --- | 1 to 60 s | 0.1 to 6 min | 1 to 60 min | 0.1 to 6 h | 1 to 60 h |
H3AM-[][][]-C | 12 | 0.2 to12 s | 2 to 120 s | 0.2 to 12 min | 2 to 120 min | 0.2 to 12 h | --- |
Note: Instantaneous output is obtained by turning the time setting knob below "0" until the time setting knob stops.
Rated supply voltage | 100 to 240 VAC (50/60 Hz) |
---|---|
Operating voltage range | 85% to 110% of rated supply voltage |
Power reset (-NS) | Minimum power-opening time: 0.5 s |
Reset input time (-NSR) | Minimum input time: 0.5 s |
Reset voltage range (-NSR) | H level: 85 to 264 VAC
L level: 0 to 10 VAC |
Power consumption | Approx. 9 VA (Approx. 5 W) |
Control output | Relays in H3AM-NS (R1) (R2)
Relay in H3AM-NS (R2) (Contact material: AgSnIn) Contact output: 5 A at 250 VAC, resistive load (cosφ = 1) The minimum applicable load: 10 mA at 5 VDC (failure level: P, reference value) Relay in H3AM-NSR (R1) (Contact material: AgSnIn) Contact output: 5 A at 250 VAC, resistive load (cosφ = 1) The minimum applicable load: 100 mA at 5 VDC (failure level: P, reference value) |
Ambient temperature | Operating: -10°C to 55°C (with no icing)
Storage: -25°C to 65°C (with no icing) |
Ambient humidity | Operating: 35% to 85% |
Accuracy of operating
time |
±0.7% FS max. |
---|---|
Setting error | ±2% FS max. |
Reset time | Power reset: 0.5 s max.
Reset input time: 0.5 s max. |
Influence of voltage | ±1% FS max. |
Influence of
temperature |
±2% FS max. |
Insulation resistance | 100 MΩ max. (at 500 VDC) |
Dielectric strength | 2,000 VAC (50/60 Hz) for 1 min between exposed non-current-carrying metal parts and
current-carrying metal parts 2,000 VAC (50/60 Hz) for 1 min between the operating circuit and control output terminals 1,000 VAC (50/60 Hz) for 1 min between the operating power supply circuit and reset input circuit (H3AM-NSR only) 1,000 VAC (50/60 Hz) for 1 min between contacts not located next to each other 2,000 VAC (50/60 Hz) for 1 min between contacts of opposite poles |
Impulse withstand
voltage |
5 kV between power terminals
5 kV between exposed non-current-carrying metal parts and current-carrying metal parts |
Noise immunity | ±1.5 kV (between power terminals) square-wave noise by a noise simulator
(pulse width: 100 ns/1 μs, 1-ns rise) |
Static immunity | Malfunction: 8 kV
Destruction: 15 kV |
Vibration resistance | Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 2 cycles each in 3 directions (8 min
per cycle) Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 2 cycles each in 3 directions (8 min per cycle) |
Shock resistance | Destruction: 300 m/s2 3 times each in 6 directions
Malfunction: 150 m/s2 (100 m/s2 in the front/back direction) 3 times each in 6 directions |
Life expectancy | Mechanical: 5,000,000 times min. (under no load at 1,800 times/h)
Electrical: 100,000 times min. (5-A at 250 VAC, resistive load at 1,800 times/h) |
Motor life expectancy | 20,000 h |
EMC | (EMI): EN61812-1
Emission Enclosure: EN55011 class A Emission AC Mains: EN55011 class A (EMS): EN61812-1 Immunity ESD: IEC61000-4-2 Immunity RF-interference: IEC61000-4-3 Immunity Burst: IEC61000-4-4 Immunity Surge: IEC61000-4-5 Immunity Conducted Disturbance: IEC61000-4-6 Immunity Power Frequency Magnetic Fields: IEC61000-4-8 Immunity Voltage Dip/Interruption: IEC61000-4-11 |
Enclosure rating | IP65 (front panel only) * IP20 (terminal section) |
Weight | Approx. 350 g |
last update: June 10, 2014