Page top

Industrial Automation

Industrial Automation

MY

Miniature Power Relays

MY

Best-selling, general-purpose relays that can be selected based on operating environment and application

MY Miniature Power Relays

Ratings

Operating Coils

Terminal Type Classification Number
of poles
Contacts Without operation
indicator
With operation
indicator
Plug-in terminals Standard models 2 Single MY2 MY2N
4 Single MY4 MY4N
Bifurcated MY4Z MY4ZN
Models with built-in diode for
coil surge absorption
(DC coil specification only)
2 Single MY2-D MY2N-D2
4 Single MY4-D MY4N-D2
Bifurcated MY4Z-D MY4ZN-D2
Models with built-in CR circuit
for coil surge absorption
(AC coil specification only)
2 Single MY2-CR MY2N-CR
4 Single MY4-CR MY4N-CR
Bifurcated MY4Z-CR MY4ZN-CR

Item Rated current
(mA)
Coil
resistance
 (Ω)
Coil inductance (H) Must
operate
voltage
(V)
Must
release
voltage
(V)
Maximum
voltage
(V)
Power
consumption
(VA, W)
Rated voltage
(V)
50 Hz 60 Hz Armature
OFF
Armature
ON
AC 12 106.5 91 46 0.17 0.33 80%
max.
*1
30%
min.
*2
110% of
rated
voltage
Approx. 0.9
to 1.3
(at 60 Hz)
24 53.8 46 180 0.69 1.3
100/110 11.7/12.9 10/11 3,750 14.54 24.6
110/120 9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220 6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240 4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC 12 72.7 165 0.73 1.37 10%
min.
*2
Approx. 0.9
24 36.3 662 3.2 5.72
48 17.6 2,725 10.6 21.0
100/110 8.7/9.6 11,440 45.6 86.2

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20%
             for AC rated current and ±15% for DC coil resistance.
         2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
         3. Operating characteristics were measured at a coil temperature of 23°C.
         4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1.There is variation between products, but actual values are 80% maximum.
     To ensure operation, apply at least 80% of the rated value (at a coil temperature of 23°C).
*2.There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC.
     To ensure release, use a value that is lower than the specified value.

Terminal Type Classification Number
of poles
Contacts Without operation
indicator
With operation
indicator
Plug-in terminals Standard models 2 Bifurcated MY2Z MY2ZN
Models with built-in diode for
coil surge absorption
(DC coil specification only)
2 Bifurcated MY2Z-D MY2ZN-D2
3 Single MY3-D MY3N-D2
Models with built-in CR circuit
for coil surge absorption
(AC coil specification only)
2 Bifurcated MY2Z-CR MY2ZN-CR

Item Rated current
(mA)
Coil
resistance
(Ω)
Coil inductance (H) Must
operate
voltage
(V)
Must
release
voltage
(V)
Maximum
voltage
(V)
Power
consumption
(VA, W)
Rated voltage
(V)
50 Hz 60 Hz Armature
OFF
Armature
ON
AC 12 106.5 91 46 0.17 0.33 80%
max.
*1
30%
min.
*2
110% of
rated
voltage
Approx. 0.9
to 1.3
(at 60 Hz)
24 53.8 46 180 0.69 1.3
100/110 11.7/12.9 10/11 3,750 14.54 24.6
110/120 9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220 6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240 4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC 12 75 160 0.73 1.37 10%
min.
*2
Approx. 0.9
24 36.9 650 3.2 5.72
48 18.5 2,600 10.6 21.0
100/110 9.1/10 11,000 45.6 86.2

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20%
             for AC rated current and ±15% for DC coil resistance.
         2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
         3. Operating characteristics were measured at a coil temperature of 23°C.
         4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1.There is variation between products, but actual values are 80% maximum.
     To ensure operation, apply at least 80% of the rated value.
*2.There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC.
     To ensure release, use a value that is lower than the specified value.

Terminal Type Classification Number of poles Contacts With latching lever
Plug-in terminals Standard models 2 Single MY2IN(S)
4 Single MY4IN(S)
Bifurcated MY4ZIN(S)
Models with built-in diode for
coil surge absorption
(DC coil specification only)
2 Single MY2IN-D2(S)
4 Single MY4IN-D2(S)
Bifurcated MY4ZIN-D2(S)
Models with built-in CR circuit
for coil surge absorption
(AC coil specification only)
2 Single MY4IN-CR(S)
4 Bifurcated MY4ZIN-CR(S)

Item Rated current
(mA)
Coil
resistance
(Ω)
Coil inductance (H) Must
operate
voltage
(V)
Must
release
voltage
(V)
Maximum
voltage
(V)
Power
consumption
(VA, W)
Rated voltage
(V)
50 Hz 60 Hz Armature
OFF
Armature
ON
AC 100/110 11.7/12.9 10/11 3,750 14.54 24.6 80%
max.
*1
30%
min.
*2
110% of
rated
voltage
Approx. 0.9
to 1.3
(at 60 Hz)
200/220 6.2/6.8 5.3/5.8 12,950 54.75 94.07
DC 12 75 160 0.73 1.37 10%
min.
*2
Approx. 0.9
24 37.7 636 3.2 5.72
48 18.8 2,560 10.6 21

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20%
             for AC rated current and ±15% for DC coil resistance.
         2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
         3. Operating characteristics were measured at a coil temperature of 23°C.
         4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1.There is variation between products, but actual values are 80% maximum.
     To ensure operation, apply at least 80% of the rated value.
*2.There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC.
     To ensure release, use a value that is lower than the specified value.

Terminal Type Classification Number
of poles
Contacts Without operation
indicator
With operation
indicator
Plug-in terminals Standard models 3 Single MY3 MY3N
4 Crossbar bifurcated MY4Z-CBG MY4ZN-CBG
PCB terminals Standard models 2 Single MY2-02
3 Single MY3-02
4 Single MY4-02
Bifurcated MY4Z-02
Case-surface
mounting
Standard models 2 Single MY2F
3 Single MY3F
4 Single MY4F
Bifurcated MY4ZF

Item Rated current
(mA)
Coil
resistance
(Ω)
Coil inductance (H) Must
operate
voltage
(V)
Must
release
voltage
(V)
Maximum
voltage
(V)
Power
consumption
(VA, W)
Rated voltage
(V)
50 Hz 60 Hz Armature
OFF
Armature
ON
AC 12 106.5 91 46 0.17 0.33 80%
max.
*1
30%
min.
*2
110% of
rated
voltage
Approx. 0.9
to 1.3
(at 60 Hz)
24 53.8 46 180 0.69 1.3
100/110 11.7/12.9 10/11 3,750 14.54 24.6
110/120 9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220 6.2/6.8 5.3/5.8 12,950 54.75 94.07
220/240 4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC 12 75 160 0.73 1.37 10%
min.
*2
Approx. 0.9
24 36.9 650 3.2 5.72
48 18.5 2,600 10.6 21.0
100/110 9.1/10 11,000 45.6 86.2

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20%
             for AC rated current and ±15% for DC coil resistance.
         2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
         3. Operating characteristics were measured at a coil temperature of 23°C.
         4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1.There is variation between products, but actual values are 80% maximum.
     To ensure operation, apply at least 80% of the rated value.
*2.There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure
     release, use a value that is lower than the specified value.

Contact Ratings

Number of
poles
(contact
configuration)
2-pole (DPDT) 3-pole (3PDT)
Contact
structure
Single Bifurcated Single
With latching lever (S)
Load Resistive
load
Inductive
load
(cos φ = 0.4,
L/R = 7 ms)
Resistive
load
Inductive
load
(cos φ = 0.4,
L/R = 7 ms)
Resistive
load
Inductive
load
(cos φ = 0.4,
L/R = 7 ms)
Resistive
load
Inductive
load
(cos φ = 0.4,
L/R = 7 ms)
Rated load 5 A at
220 VAC
5 A at
24 VDC
2 A at
220 VAC
2 A at
24 VDC
5 A at
250 VAC
5 A at
30 VDC
2 A at
250 VAC
2 A at
30 VDC
5 A at
220 VAC
5 A at
24 VDC
2 A at
220 VAC
2 A at
24 VDC
5 A at
220 VAC
5 A at
24 VDC
2 A at
220 VAC
2 A at
24 VDC
Rated carry
current*1
5 A (10 A*2) 5 A 5 A
Maximum
switching
voltage
250 VAC, 125 VDC 250 VAC, 125 VDC
Maximum
switching
current
5 A 10 A 5 A 5 A
Maximum
switching
power
1,100 VA
120 W
440 VA
48 W
2,500 VA
300 W
500 VA
60 W
1,100 VA
120 W
440 VA
48 W
1,100 VA
120 W
440 VA
48 W
Contact
material
Ag Au plating + Ag Ag

Number of poles (contact configuration) 4-pole (4PDT)
Contact structure Single
With latching lever (S)
Load Resistive load Inductive load
(cos φ = 0.4,
L/R = 7 ms)
Resistive load Inductive load
(cos φ = 0.4,
L/R = 7 ms)
Rated load 3 A at 220 VAC
3 A at 24 VDC
0.8 A at 220 VAC
1.5 A at 24 VDC
3 A at 250 VAC
3 A at 30 VDC
0.8 A at 250 VAC
1.5 A at 30 VDC
Rated carry current*1 3 A (5 A*2)
Maximum switching voltage 250 VAC, 125 VDC
Maximum switching current 3 A (5 A*2)
Maximum switching power 660 VA
72 W
176 VA
36 W
1,250 VA
150 W
200 VA
45 W
Contact material Au cladding + Ag alloy (Au plating + Ag*3)

Number of poles
(contact configuration)
4-pole (4PDT)
Contact structure Bifurcated Crossbar bifurcated (CBG)
With latching lever (S)
Load Resistive
load
Inductive load
(cos φ = 0.4,
L/R = 7 ms)
Resistive
load
Inductive load
(cos φ = 0.4,
L/R = 7 ms)
Resistive
load
Inductive load
(cos φ = 0.4,
L/R = 7 ms)
Rated load 3 A at
220 VAC
3 A at
24 VDC
0.8 A at
220 VAC
1.5 A at
24 VDC
3 A at
250 VAC
3 A at
30 VDC
0.8 A at
250 VAC
1.5 A at
30 VDC
1 A at
220 VAC
1 A at
24 VDC
0.3 A at
220 VAC
0.5 A at
24 VDC
Rated carry current*1 3 A (5 A*2) 1 A
Maximum switching
voltage
250 VAC, 125 VDC
Maximum switching
current
3 A (5 A*2) 1 A
Maximum switching
power
660 VA
72 W
176 VA
36 W
1,250 VA
150 W
200 VA
45 W
220 VA
24 W
66 VA
12 W
Contact material Au cladding + Ag alloy (Au plating + Ag*3) Au cladding + AgPd

*1.If you use a Socket, do not exceed the rated carry current of the Socket.
*2.Values shown in parentheses are for the MY[](S) model with latching lever.
*3. For MY[]-02 relays with PCB terminals and MY[]F case-surface-mounting relays.

Characteristics

Number of poles (contact configuration) 2-pole (DPDT) 3-pole (3PDT)
Contact structure Single Bifurcated Single
Contact resistance*1 *2 50 mΩ max.
Operate time*3 20 ms max.
Release time*3 20 ms max.
Maximum
switching
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*4*5 100 MΩ min.
Dielectric
strength
Between coil and contacts 2,000 VAC, 50/60 Hz for 1 min
Between contacts of
different polarity
Between contacts of
the same polarity
1,000 VAC at 50/60 Hz for 1 min
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance Mechanical AC: 50,000,000
operations min.
DC: 100,000,000
operations min.
(switching frequency:
18,000 operations/h)
AC: 50,000,000
operations min.
DC: 50,000,000
operations min.
(switching frequency:
18,000 operations/h)
AC: 50,000,000
operations min.
DC: 100,000,000
operations min.
(switching frequency:
18,000 operations/h)
Electrical*6 500,000 operations
min.
(rated load, switching
frequency: 1,800
operations/h)
200,000 operations
min.
(rated load, switching
frequency: 1,800
operations/h)
500,000 operations
min.
(rated load, switching
frequency: 1,800
operations/h)
Failure rate P value (reference value)*7 1 mA at 5 VDC 100 μA at 1 VDC 1 mA at 5 VDC
Weight Approx. 35 g Approx. 35 g Approx. 35 g

Number of poles (contact configuration) 4-pole (4PDT)
Contact structure Single Bifurcated Crossbar bifurcated
(CBG)
Contact resistance*1 *2 50 mΩ max. 100 mΩ max.
Operate time*3 20 ms max.
Release time*3 20 ms max.
Maximum
switching
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*4*5 100 MΩ min.
Dielectric
strength
Between coil and contacts 2,000 VAC, 50/60 Hz for 1 min
Between contacts of
different polarity
Between contacts of
the same polarity
1,000 VAC at 50/60 Hz for 1 min 700 VAC at 50/60 Hz
for 1 min
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance Mechanical AC: 50,000,000
operations min.
DC: 100,000,000
operations min.
(switching frequency:
18,000 operations/h)
AC: 20,000,000
operations min.
DC: 20,000,000
operations min.
(switching frequency:
18,000 operations/h)
AC: 5,000,000
operations min.
DC: 5,000,000
operations min.
(switching frequency:
18,000 operations/h)
Electrical*6 200,000 operations
min.
(rated load, switching
frequency: 1,800
operations/h)
100,000 operations
min.
(rated load, switching
frequency: 1,800
operations/h)
50,000 operations min.
(rated load, switching
frequency: 1,800
operations/h)
Failure rate P value (reference value)*7 1 mA at 1 VDC 100 μA at 1 VDC 100 μA at 1 VDC
Weight Approx. 35 g Approx. 35 g Approx. 35 g

Note: The data shown above are initial values.
*1. Models with latching lever are 100 mΩ maximum.
*2. Measurement conditions: 1 A at 5 VDC using the voltage drop method.
*3. Measurement conditions: With rated operating power applied, not including contact bounce.
*4. Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*5. Models with latching lever are 1,000 mΩ minimum.
*6. Ambient temperature condition: 23°C
*7. This value was measured at a switching frequency of 120 operations per minute.

Classification Standard models Models with built-in diode for coil
surge absorption (-D)/ Models with
built-in CR circuit for coil surge
absorption (-CR)
Contacts Single/bifurcated Crossbar/bifurcated
(CBG)
Single/bifurcated
Features Without
operation
indicator
With operation indicator Without
operation
indicator
With
operation
indicator
Without
operation
indicator
With operation indicator
With
latching
lever
With
latching
lever
Ambient
operating
temperature
*1
-55 to
70°C
-55 to 60°C
*2
-55 to 70°C -25 to
70°C
-25 to
60°C
-55 to
60°C *2
-55 to 60°C
*2
-55 to 70°C
Ambient
operating
humidity
5% to 85% 5% to 85%

*1.With no icing or condensation.
*2.This limitation is due to the diode junction temperature and elements used.

Certified Standards

UL certification (File No. E41515)

Model Standard
number
Category Listed/
Recognized
Operating
Coil ratings
No. of
poles
Contact ratings Certified
number of
operations
MY2
MY2N
MY2IN(S)
MY2-D
MY2N-D2
MY2IN-D2(S)
MY2-CR
MY2N-CR
UL508 NRNT2 Recognition 6 to 240 VAC
6 to 125 VDC
2 10 A, 250 VAC (General Use)
10 A, 30 VDC (General Use)
7 A, 240 VAC (General Use)
7 A, 24 VDC (Resistive)
5 A, 240 VAC (General Use)
5 A, 250 VAC (Resistive)
5 A, 30 VDC (Resistive)
3 A, 265 VAC (Resistive)
6,000
1/6 HP, 250 VAC
1/8 HP, 265 VAC
1/10 HP, 120 VAC
1,000
B300 Pilot Duty
(Same polarity)
6,000
MY2Z
MY2ZN
MY2-02
MY2F
MY2Z-D
MY2ZN-D2
MY2Z-CR
MY2ZN-CR
UL508 NRNT2 Recognition 6 to 240 VAC
6 to 125 VDC
2 7 A, 240 VAC (General Use)
7 A, 24 VDC (Resistive)
5 A, 240 VAC (General Use)
5 A, 250 VAC (Resistive)
5 A, 30 VDC (Resistive)
3 A, 265 VAC (Resistive)
6,000
1/6 HP, 250 VAC
1/8 HP, 265 VAC
1/10 HP, 120 VAC
1,000
B300 Pilot Duty
(Same polarity)
6,000
MY3
MY3N
MY3-D
MY3N-D2
MY3-02
MY3F
UL508 NRNT2 Recognition 6 to 240 VAC
6 to 125 VDC
3 5 A, 28 VDC (Resistive)
5 A, 240 VAC (General Use)
6,000
1/6 HP, 250 VAC 1,000
MY4
MY4N
MY4IN(S)
MY4-D
MY4N-D2
MY4IN-D2(S)
MY4Z
MY4ZN
MY4ZIN(S)
MY4Z-D
MY4ZN-D2
MY4ZIN-D2(S)
MY4Z-CR
MY4ZN-CR
MY4ZIN-CR(S)
MY4-02
MY4F
MY4Z-02
MY4ZF
UL508 NRNT2 Recognition 6 to 240 VAC
6 to 125 VDC
4 5 A, 28 VDC (General Use)
(Same polarity)
5 A, 240 VAC (General Use)
(Same polarity)
5 A, 30 VDC (Resistive)
(Same polarity)
5 A, 250 VAC (Resistive)
(Same polarity)
0.2 A, 120 VDC (Resistive)
(Same polarity)
6,000
1/6 HP, 250 VAC
(Same polarity)
1/10 HP, 120 VAC
(Same polarity)
1,000
B300 Pilot Duty
(Same polarity)
6,000

CSA certification (File No. LR31928)

Model Standard
number
Class
number
Operating
Coil ratings
No. of
poles
Contact ratings Certified
number of
operations
MY2
MY2N
MY2IN(S)
MY2-D
MY2N-D2
MY2IN-D2(S)
MY2-CR
MY2N-CR
C22.2 No.0,
No.14
6 to 240 VAC
6 to 125 VDC
2 7 A, 240 VAC (Resistive)
7 A, 24 VDC (Resistive)
5 A, 240 VAC (General Use)
5 A, 250 VAC (Resistive)
5 A, 30 VDC (Resistive)
6,000
1/6 HP, 250 VAC (Same polarity)
1/10 HP, 120 VAC (Same polarity)
1,000
MY2Z
MY2ZN
MY2-02
MY2F
MY2Z-D
MY2ZN-D2
MY2Z-CR
MY2ZN-CR
C22.2 No.0,
No.14
6 to 240 VAC
6 to 125 VDC
2 7 A, 240 VAC (General Use)
(Same polarity)
7 A, 24 VDC (Resistive)
(Same polarity)
5 A, 240 VAC (General Use)
(Same polarity)
5 A, 30 VDC (Resistive)
5 A, 250 VAC (Resistive)
(Same polarity)
0.2 A, 120 VDC (Resistive)
6,000
1/6 HP, 250 VAC
1/10 HP, 120 VAC
1,000
MY3
MY3N
MY3-D
MY3N-D2
MY3-02
MY3F
C22.2 No.0,
No.14
6 to 240 VAC
6 to 125 VDC
3 5 A, 28 VDC (Resistive)
5 A, 240 VAC (General Use)
7 A, 240 VAC (General Use)
7 A, 24 VDC (Resistive)
6,000
1/6 HP, 250 VAC 1,000
MY4
MY4N
MY4N(S)
MY4-D
MY4N-D2
MY4IN-D2(S)
MY4-CR
MY4N-CR
MY4IN-CR(S)
MY4Z
MY4ZN
MY4ZIN(S)
MY4Z-D
MY4ZN-D2
MY4ZIN-D2(S)
MY4Z-C
MY4ZN-CR
MY4ZIN-CR(S)
C22.2 No.14 3211 07 6 to 240 VAC
6 to 125 VDC
4 5 A, 240 VAC (General Use)
(Same polarity)
5 A, 28 VDC (General Use)
(Same polarity)
5 A, 250 VAC (Resistive)
(Same polarity)
5 A, 30 VDC (Resistive)
(Same polarity)
0.2 A, 120 VDC (Resistive)
(Same polarity)
6,000
1/6 HP, 250 VAC (Same polarity)
1/10 HP, 120 VAC (Same polarity)
1,000
B300 Pilot Duty (Same polarity) 6,000
MY4-02
MY4F
MY4Z-02
MY4ZF
C22.2 No.0,
No.14
3211 07 6 to 240 VAC
6 to 125 VDC
4 7 A, 240 VAC (General Use)
(Same polarity)
7 A, 24 VDC (Resistive)
(Same polarity)
5 A, 240 VAC (General Use)
(Same polarity)
5 A, 30 VDC (Resistive)
5 A, 250 VAC (Resistive)
(Same polarity)
0.2 A, 120 VDC (Resistive)
6,000
1/6 HP, 250 VAC
1/10 HP, 120 VAC
1,000

TÜV Rheinland certification (Certification No. R50030059)

Model Operating Coil ratings Contact ratings Certified number of operations
MY2Z
MY2ZN
MY2-02
MY2F
MY2Z-D
MY2ZN-D2
MY2Z-CR
MY2ZN-CR
6 to 125 VDC,
6 to 240 VAC
5 A, 250 VAC (cos φ = 1.0) 100,000
MY3
MY3N
MY3-D
MY3N-D2
MY3-02
MY3F
5 A, 250 VAC (cos φ = 1.0)
0.8 A, 250 VAC (cos φ = 0.4)
MY4-02
MY4F
MY4Z-02
MY4ZF
3 A, 120 VAC (cos φ = 1.0)
0.8 A, 250 VAC (cos φ = 0.4)

CE Marking

Model EMC Directive Low Voltage Directive Machinery Directive Safety Category
MY2
MY2N
MY2IN(S)
MY2Z
MY2ZN
MY2-D
MY2N-D2
MY2IN-D2(S)
MY2-CR
MY2N-CR
MY2Z-CR
MY2ZN-CR
MY2Z-D
MY2ZN-D2
MY2F
Not applicable Applicable Not applicable 1
MY3
MY3N
MY3-D
MY3N-D2
MY3F
MY4
MY4N
MY4IN(S)
MY4Z
MY4ZN
MY4ZIN(S)
MY4-D
MY4N-D2
MY4IN-D2(S)
MY4Z-D
MY4ZN-D2
MY4ZIN-D2(S)
MY4-CR
MY4N-CR
MY4Z-CR
MY4ZN-CR
MY4F
MY4ZF

LR certification (Lloyd’s Register)

Model File No. Environmental
Category
Operating
Coil ratings
Contact ratings Certified number
of operations
MY2
MY2N
MY2IN(S)
MY2-D
MY2N-D2
MY2IN-D2(S)
MY2-CR
MY2N-CR
File No.98/10014 ENV2,3 6 to 240 VAC
6 to 125 VDC
10 A, 250 VAC (Resistive)
2 A, 250 VAC (PF0.4)
10 A, 30 VDC (Resistive)
2 A, 30 VDC (L/R = 7 ms)
MY2:
50,000
MY2Z
MY2ZN
MY2Z-D
MY2ZN-D2
File No.90/10270 ENV2,3 6 to 240 VAC
6 to 125 VDC
2 A, 30 VDC inductive load
2 A, 200 VAC inductive load
MY2:
50,000
MY4
MY4N
MY4IN(S)
MY4-D
MY4N-D2
MY4IN-D2(S)
MY4-CR
MY4N-CR
MY4IN-CR(S)
MY4Z
MY4ZN
MY4ZIN(S)
MY4Z-D
MY4ZN-D2
MY4ZIN-D2(S)
MY4Z-CR
MY4ZN-CR
MY4ZIN-CR(S)
File No.98/10014 ENV2,3 6 to 240 VAC
6 to 125 VDC
5 A, 250 VAC (Resistive)
0.8 A, 250 VAC (PF0.4)
5 A, 30 VDC (Resistive)
1.5 A, 30 VDC (L/R = 7 ms)
MY4:
50,000

VDE certification

Model Standard
number
Certification No. Operating
Coil ratings
Contact ratings Certified number
of operations
MY2
MY2N
MY2IN(S)
MY2-D
MY2N-D2
MY2IN-D2(S)
MY2-CR
MY2N-CR
EN 61810-1 112467UG 6, 12, 24,
48/50,
100/110,
110/120,
200/220,
220/240 VAC
6, 12, 24,
48, 100/110,
125 VDC
10A, 250 VAC (cos φ = 1)
10A, 30 VDC (L/R = 0 ms)
MY2:
100,000
MY4:
100,000
MY4Z:
50,000 (AC)
MY4
MY4N
MY4IN(S)
MY4Z
MY4ZN
MY4ZIN(S)
MY4-D
MY4N-D2
MY4IN-D2(S)
MY4Z-D
MY4ZN-D2
MY4ZIN-D2(S)
MY4-CR
MY4N-CR
MY4IN-CR(S)
MY4Z-CR
MY4ZN-CR
MY4ZIN-CR(S)
6, 12, 24,
48/50,
100/110,
110/120,
200/220,
220/240 VAC
6, 12, 24,
48, 100/110,
125 VDC
5 A, 250 VAC (cos φ = 1)
5 A, 30 VDC (L/R = 0 ms)

MYK Miniature Power Latching Relays

Ratings

Operating coil

Rated
voltage
(V)
Set coil Reset coil Must
operate
voltage
(V)
Must
release
voltage
(V)
Maximum
voltage
(V)
Power consumption
(VA, W)
Rated current
(mA)
Coil
resistance
(Ω)
Rated current
(mA)
Coil
resistance
(Ω)
Set coil Reset coil
50 Hz 60 Hz 50 Hz 60 Hz
AC 12 57 56 72 39 38.2 130 80%
max.*
80%
max.
110%
max. of
rated
voltage
Approx.
0.6 to
0.9 (at
60 Hz)
Approx.
0.2 to
0.5 (at
60 Hz)
24 27.4 26.4 320 18.6 18.1 550
100 7.1 6.9 5,400 3.5 3.4 3,000
DC 12 110 110 50 235 Approx.
1.3
Approx.
0.6
24 52 470 25 940
48 27 1,800 16 3,000

Note: 1. The rated current for AC is the value measured with a DC ammeter in half-wave rectification.
         2. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20%
             for AC rated current and ±15% for DC coil resistance.
         3. The AC coil resistance is a reference value only.
         4. Operating characteristics were measured at a coil temperature of 23°C.
         5. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*There is variation between products, but actual values are 80% maximum.

Contact Ratings

Number of poles (contact configuration) 2-pole (DPDT)
Contact structure Single
Load Resistive load Inductive load (cos φ = 0.4, L/R = 7 ms)
Rated load 3 A at 220 VAC
3 A at 24 VDC
0.8 A at 220 VAC
1.5 A at 24 VDC
Rated carry current 3 A
Maximum switching voltage 250 VAC, 125 VDC
Maximum switching current 3 A
Maximum switching power 660 VA
72 W
176 VA
36 W
Contact material Au plating + Ag

Characteristics

Contact resistance*1 50 mΩ max.
Set Operate time*2 AC: 30 ms max., DC: 15 ms max.
Minimum pulse width AC: 60 ms, DC: 30 ms
Reset Release time*2 AC: 30 ms max., DC: 15 ms max.
Minimum pulse width AC: 60 ms, DC: 30 ms
Maximum
switching
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*3 100 MΩ min.
Dielectric
strength
Between coil and contacts
Between contacts of
different polarity
1,500 VAC at 50/60 Hz for 1 min
Between contacts of the
same polarity
1,000 VAC at 50/60 Hz for 1 min
Between set/reset coils
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance Mechanical 100,000,000 operations min. (switching frequency: 18,000 operations/h)
Electrical*4 200,000 operations min. (at rated load, switching frequency: 1,800
operations/h)
Failure rate P value (reference value)*5 1 mA at 1 VDC
Ambient operating temperature*6 -55 to 60°C
Ambient operating humidity 5% to 85%
Weight Approx. 30 g

Note: The data shown above are initial values.
*1.Measurement conditions: 1 A at 5 VDC using the voltage drop method.
*2.Measurement conditions: With rated operating power applied, not including contact bounce.
*3.Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4.Ambient temperature condition: 23°C
*5.This value was measured at a switching frequency of 120 operations per minute.
*6.With no icing or condensation.

MYQ/MYH Miniature Power Sealed Relays

Operating coil

Rated
voltage
(V)
Rated current
(mA)
Coil
resistance
(Ω)
Coil inductance (H) Must
operate
voltage
(V)*1
Must
release
voltage
(V)*2
Maximum
voltage
(V)
Power
consumption
(VA, W)
50 Hz 60 Hz Armature
OFF
Armature
ON
AC 24 53.8 46 180 0.69 1.3 80%
max.
30%
min.
110%
max. of
rated
voltage
Approx. 0.9
to 1.3
(at 60 Hz)
100/110 11.7/12.9 10/11 3,750 14.54 24.6
110/120 9.9/10.8 8.4/9.2 4,430 19.2 32.1
200/220 6.2/6.8 5.3/5.8 12,950 54.75 91.07
220/240 4.8/5.3 4.2/4.6 18,790 83.5 136.4
DC 12 75 165 0.734 1.37 10%
min.
Approx. 0.9
24 36.9 650 3.2 5.72
48 18.5 2,600 10.6 21.0
100/110 9.1/10 11,000 45.6 86.0

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20%
             for AC rated current and ±15% for DC coil resistance.
         2. The AC coil resistance and coil inductance values are for reference only.
         3. Operating characteristics were measured at a coil temperature of 23°C.
         4. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1.There is variation between products, but actual values are 80% maximum. To ensure operation, apply at least 80% of
     the rated value.
*2.There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure
     release, use a value that is lower than the specified value.

Contact Ratings

Plastic Sealed Relays: MYQ

Number of poles (contact configuration) 4-pole (4PDT)
Contact structure Single/bifurcated
Load Resistive load Inductive load (cos φ = 0.4, L/R = 7 ms)
Rated load 1 A at 220 VAC
1 A at 24 VDC
0.5 A at 220 VAC
0.5 A at 24 VDC
Rated carry current 1 A
Maximum switching voltage 250 VAC
125 VDC
Maximum switching current 1 A
Maximum switching power 220 VA
24 W
110 VA
12 W
Contact material Au plating + Ag

Hermetically Sealed Relays: MYH

Number of poles
(contact configuration)
4-pole (4PDT)
Contact structure Single Bifurcated
Load Resistive load Inductive load
(cos φ = 0.4,
L/R = 7 ms)
Resistive load Inductive load
(cos φ = 0.4,
L/R = 7 ms)
Rated load 3 A at 110 VAC
3 A at 24 VDC
0.8 A at 110 VAC
1.5 A at 24 VDC
3 A at 110 VAC
3 A at 24 VDC
0.8 A at 110 VAC
1.5 A at 24 VDC
Rated carry current 3 A
Maximum switching voltage 125 VAC
125 VDC
Maximum switching current 3 A
Maximum switching power 330 VA
72 W
88 VA
36 W
330 VA
72 W
88 VA
36 W
Contact material Au plating + Ag

Characteristics

Model MYQ MYH
Contact resistance*1 50 mΩ max.
Operate time*2 20 ms max.
Release time*2 20 ms max.
Maximum
switching
frequency
Mechanical 18,000 operations/h
Rated load 1,800 operations/h
Insulation resistance*3 100 MΩ min.
Dielectric
strength
Between coil and
contacts
1,500 VAC at 50/60 Hz for 1 min 1,000 VAC at 50/60 Hz for 1 min
Between contacts
of different polarity
1,500 VAC at 50/60 Hz for 1 min 1,000 VAC at 50/60 Hz for 1 min
Between contacts
of the same polarity
1,000 VAC at 50/60 Hz for 1 min 700 VAC at 50/60 Hz for 1 min
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock
resistance
Destruction 1,000 m/s2
Malfunction 200 m/s2
Endurance Mechanical Single contacts:
AC: 50,000,000 operations min.,
DC: 100,000,000 operations min.
Bifurcated contacts:
5,000,000 operations min.,
DC: 5,000,000 operations min.
(switching frequency: 18,000
operations/h)
Single contacts:
50,000,000 operations min.
Bifurcated contacts:
5,000,000 operations min.
(switching frequency: 18,000
operations/h)
Electrical*4 Single contacts:
200,000 operations min.
Bifurcated contacts:
100,000 operations min.
(at rated load, switching frequency:
1,800 operations/h)
Single contacts:
100,000 operations min.
Bifurcated contacts:
50,000 operations min.
(at rated load, switching frequency:
1,800 operations/h)
Failure rate P Level (reference
value)*5
Single contacts: 1 mA at 1 VDC
Bifurcated contacts: 100 μA at 1 VDC
Single contacts: 100 μA at 1 VDC
Bifurcated contacts: 100 μA at 100 mVDC
Ambient operating temperature*6 -55 to 60°C -25 to 60°C
Ambient operating humidity 5% to 85%
Weight Approx. 35 g Approx. 50 g

Note: The data shown above are initial values.
*1.Measurement conditions: 1 A at 5 VDC using the voltage drop method.
*2.Measurement conditions: With rated operating power applied, not including contact bounce.
     Ambient temperature condition:23°C
*3.Measurement conditions: For 500 VDC applied to the same location as for dielectric strength measurement.
*4.Ambient temperature condition:23°C
*5.This value was measured at a switching frequency of 120 operations per minute.
*6.With no icing or condensation.

Common Options (Order Separately)

Characteristics

Sockets

MY Specifications 48

Socket Accessories

For Front-connecting Sockets

Short Bars

Application Applicable
sockets
Model Maximum
carry current
Ambient operating
temperature
Ambient operating
humidity
Bridging contact
terminals
(common)
PYF-08-PU(-L)
PYF-14-PU(-L)
PYDN-7.75-020[] 20 A -40 to 70°C 5% to 85%
PYDN-7.75-030[]
PYDN-7.75-040[]
PYDN-7.75-200[]
PYFZ-08
PYD-025B[] 20 A
(However,
18 A when 70°C)
-40 to 70°C
(with no icing or
condensation)
45% to 85%
(with no icing or
condensation)
PYD-085B[]
PYFZ-14
PYD-026B[]
PYD-086B[]
PYD-020B[]
PYD-030B[]
For Coil terminals PYF-08-PU(-L)
PYF-14-PU(-L)
PYDN-31.0-080[] 20 A -40 to 70°C 5% to 85%
PYF08S PYDM-08S[] 10 A -40 to 70°C 5% to 85%
PYF14S PYDM-14S[] 10 A -40 to 70°C 5% to 85%

Certified Standards

CSA certification (File No. LR031928)

Model Ratings Class number Standard number
PYF-08-PU 10 A, 250 V 3211 07 CSA C22.2 No14
PYF-14-PU 6 A, 250 V*
PYF08S 10 A, 250 V
PYF14S 5 A, 250 V
PYFZ-08(-E) 10 A, 250 V
PYFZ-14(-E) 6 A, 250 V
PY[]
PYF[]A
7 A, 250 V

* When power is supplied to all four poles, use with a total power current that does not exceed 20 A.

UL certification (File No. E87929)

Model Ratings Standard number Category Listed/Recognized
PYF-08-PU 10 A, 250 V UL508 SWIV2 Recognition
PYF-14-PU 6 A, 250 V*
PYF08S
PYF14S
10 A, 250 V
PYFZ-08(-E) 10 A, 250 V
PYFZ-14(-E) 6 A, 250 V
PY[]
PYF[]A
7 A, 250 V

* When power is supplied to all four poles, use with a total power current that does not exceed 20 A.

TÜV Rheinland certification

Model Ratings Standard number Certification No.
PYF-08-PU 10 A, 250 V* EN 61984 R50327595
PYF-14-PU 6 A, 250 V
PYFZ-08(-E) 10 A, 250 V R50405329
PYFZ-14(-E) 6 A, 250 V

*Ratings are for an ambient temperature of 55°C or below. At an ambient temperature of 70°C, the value is 7 A.

VDE certification

Model Standard number Certification No.
PYF08S VDE0627 (EN61984) 40015509
PYF14