CS1W-AT2[][]

C200H I/O Terminal Block Conversion Adapter

CS1W-AT2[][]

Easy and secure replacement by reusing the I/O terminal block wiring

Connection of I/O Units and Terminal Block Conversion Adapter

C200H
I/O
Terminal
Conver-
sion
Adapter
Model
Replaced from: C200H-series I/O Units Replaced to: CS-series I/O Units
Product
name
Specifications Model Product
name
Specifications Model
CS1W-
AT201
DC Input
Unit
12 to 24 VDC, 8 inputs C200H-ID211 DC Input
Unit
7 mA at 24 VDC,
16 inputs
CS1W-ID211
AC Input
Unit
100 to 120 VAC,
8 inputs
C200H-IA121 AC Input
Unit
100 to 120 VAC,
100 to 120 VDC,
16 inputs
CS1W-IA111
200 to 240 VAC,
8 inputs
C200H-IA221 200 to 240 VAC,
16 inputs
CS1W-IA211
AC/DC
Input Unit
12 to 24 VAC/VDC,
8 inputs
C200H-IM211 AC/DC
Input Unit
7 mA at 24 VDC,
16 inputs
CS1W-ID211
*1
Non-voltage contacts,
8 inputs, NPN
C200H-ID001 CS1W-ID211
*2
Non-voltage contacts,
8 inputs, PNP
C200H-ID002 CS1W-ID211
*2
Interrupt
Input Unit
12 to 24 VDC,
8 inputs
C200HS-INT01 Interrupt
Input Unit
7 mA at 24 VDC,
16 inputs
CS1W-INT01
*3
Triac
Output
Unit
1.2 A at 250 VAC max.,
8 outputs
C200H-OA223 Triac
Output
Unit
0.5 A at 250 VAC max.,
16 outputs
CS1W-OA211
*4
1 A at 120 VAC max.,
8 outputs
C200H-OA121-E 0.5 A at 250 VAC max.,
16 outputs
CS1W-OA211
1 A at 250 VAC max.,
8 outputs
C200H-OA221 CS1W-OA211
*4
Relay
Output
Unit
2 A at 250 VAC/
24 VDC max., 8 outputs
C200H-OC221 Relay
Output
Unit
2 A at 250 VAC/
24 VDC max.,
0.1 A at 120 VDC,
16 outputs
CS1W-OC211
2 A at 250 VAC/
24 VDC max.,
independent contacts,
5 outputs
C200H-OC223 2 A at 250 VAC/
24 VDC max.,
0.1 A at 120 VDC,
independent contacts,
8 outputs
CS1W-OC201
Transistor
Output
Unit
1 A at 12 to 48 VDC,
8 outputs, sinking
C200H-OD411 Transistor
Output
Unit
0.5 A at 12 to 24 VDC,
16 outputs
CS1W-OD211
*4 *5
2.1 A at 24 VDC,
8 outputs, sinking
C200H-OD213 CS1W-OD211
*4
0.8 A at 24 VDC,
8 outputs, sourcing
C200H-OD214 0.5 A at 24 VDC,
16 outputs
CS1W-OD212
*6
0.3 A at 5 to 24 VDC,
8 outputs, sourcing
C200H-OD216 CS1W-OD212
*7
CS1W-
AT211
DC Input
Unit
24 VDC, 16 inputs C200H-ID212 DC Input
Unit
7 mA at 24 VDC,
16 inputs
CS1W-ID211
AC Input
Unit
100 to 120 VAC,
16 inputs
C200H-IA122 AC Input
Unit
100 to 120 VAC,
100 to 120 VDC,
16 inputs
CS1W-IA111
100 to 120 VAC,
16 inputs
C200H-IA122V CS1W-IA111
200 to 240 VAC,
16 inputs
C200H-IA222 200 to 240 VAC,
16 inputs
CS1W-IA211
200 to 240 VAC,
16 inputs
C200H-IA222V CS1W-IA211
AC/DC
Input Unit
24 VAC/VDC, 16 inputs C200H-IM212 AC/DC
Input Unit
7 mA at 24 VDC,
16 inputs
CS1W-ID211
*1
Relay
Output
Unit
2 A at 250 VAC/
24 VDC max., 16 outputs
C200H-OC226 Relay
Output
Unit
2 A at 250 VAC/
24 VDC max.,
0.1 A at 120 VDC,
16 outputs
CS1W-OC211
2 A at 250 VAC/
24 VDC max., 16 outputs
C200H-OC226N CS1W-OC211
2 A at 250 VAC/
24 VDC max., 12 outputs
C200H-OC222 CS1W-OC211
2 A at 250 VAC/
24 VDC max., 12 outputs
C200H-OC222V CS1W-OC211
2 A at 250 VAC/
24 VDC max., 12 outputs
C200H-OC222N CS1W-OC211
2 A at 250 VAC/
24 VDC max., 16 outputs
C200H-OC225 CS1W-OC211
Transistor
Output
Unit
0.3 A at 24 VDC,
12 outputs, sinking
C200H-OD211 Transistor
Output
Unit
0.5 A at 12 to 24 VDC,
16 outputs
CS1W-OD211
0.3 A at 24 VDC,
16 outputs, sinking
C200H-OD212 CS1W-OD211
0.3 A at 5 to 24 VDC,
12 outputs, sourcing
C200H-OD217 0.5 A at 24 VDC,
16 outputs
CS1W-OD212
*8
1 A at 24 VDC,
16 outputs, sourcing,
load short-circuit
protection
C200H-OD21A CS1W-OD212
*9
Triac
Output
Unit
0.8 A at 250 VAC max,
16 outputs
C200H-OA225 Triac
Output
Unit
0.5 A at 250 VAC max.,
16 outputs
CS1W-OA211
0.3 A at 250 VAC max,
12 outputs
C200H-OA222 CS1W-OA211
0.3 A at 250 VAC max,
12 outputs
C200H-OA222V CS1W-OA211
0.5 A at 250 VAC max,
12 outputs
C200H-OA224 CS1W-OA211
CS1W-
AT202
Relay
Output
Unit
2 A at 250 VAC/
24 VDC max.,
independent contacts,
8 outputs
C200H-OC224 Relay
Output
Unit
2 A at 250 VAC/
24 VDC max.,
0.1 A at 120 VDC,
independent contacts,
8 outputs
CS1W-OC201
2 A at 250 VAC/
24 VDC max.,
independent contacts,
8 outputs
C200H-OC224V CS1W-OC201
2 A at 250 VAC/
24 VDC max.,
independent contacts,
8 outputs
C200H-OC224N CS1W-OC201

*1. 24 VDC only
*2. Need to add 24 VDC power supply.
*3. There is a restriction to the number of mountable units.
*4. The blown fuse detection bit (Bit 08) cannot be used.
*5. 12 to 24 VDC only
*6. The alarm bits (Bit 08, 09, 10, and 11) cannot be used.
*7. Remove the wire from A8 and connect it to A9. Connect 0 V of power supply to A8.
*8. Remove the wire from A8 and connect it to B9. Connect 0 V of power supply to A8.
*9. The alarm outputs cannot be used.