Switch Mode Power Supply (15, 30, 50, 100, 150, and 240-W Models)
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: April 2, 2018
Power ratings | 15 W | ||||||
---|---|---|---|---|---|---|---|
Output voltage | 5 V | 12 V | 15 V | 24 V | 48 V | ||
Efficiency (Typ.) | 100 VAC input | 74% | 77% | 80% | 80% | 83% | |
200 VAC input | 74% | 77% | 78% | 78% | 82% | ||
Input | Voltage *1 | 100 to 240 VAC (allowable voltage: 85 to 264 VAC or 120 to 370
VDC *6) |
|||||
Frequency *1 | 50/60 Hz (47 to 450 Hz) | ||||||
Current (Typ.) | 100 VAC input | 0.4 A | |||||
200 VAC input | 0.25 A | ||||||
Leakage
current |
100 VAC input | 0.5 mA max. | |||||
200 VAC input | 1 mA max. | ||||||
Inrush current
(Typ.) |
100 VAC input | 15 A (for a cold start at 25°C) | |||||
200 VAC input | 30 A (for a cold start at 25°C) | ||||||
Output | Voltage adjustment range *2 | ±10% (with V. ADJ) | |||||
Ripple *3 | 150 mV max. | 240 mV
max. |
300 mV
max. |
480 mV
max. |
960 mV
max. |
||
Input variation influence | 0.5% max. (with 85 to 264 VAC input at 100% load) | ||||||
Load variation influence | 2% max. (0
to 100% load, rated input voltage) |
1.5% max. (0 to 100% load, rated input voltage) | |||||
Temperature variation influence | 0.05%/°C max. | ||||||
Startup time
(Typ.) |
100 VAC input | 800 ms | |||||
Hold time (Typ.) | 100 VAC input | 20 ms | |||||
Addi-
tional func- tions |
Overload protection | 105% to 160% of rated current, voltage drop, intermittent, and
automatic reset |
|||||
Overvoltage protection *4 | Yes | ||||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | ||||||
Parallel operation | No (However, backup operation is possible; external diodes
required.) |
||||||
Other | Ambient operating temperature | -10 to 70°C (Derating is required according to the temperature.)
(with no icing or condensation) |
|||||
Storage temperature | -25 to 75°C (with no icing or condensation) | ||||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | ||||||
Dielectric strength | 3.0 kVAC for 1 min.
(between all inputs and outputs; Cutoff current: 10 mA) 2.0 kVAC for 1 min. (between all inputs and PE; Cutoff current: 10 mA) 1.0 kVAC for 1 min. (between all outputs and PE; Cutoff current: 20 mA) |
||||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminal) at
500 VDC |
||||||
Vibration resistance | 10 to 55 Hz, 19.6 m/s2 (2 G) for 1 h each in X, Y, and Z directions | ||||||
Shock resistance | 196.1 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||||
EMI | Conducted Emissions | Conforms to EN 55011 Group 1 Class B *7 | |||||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *7 | ||||||
EMS | Electrostatic
Discharge |
Conforms to EN61000-4-2 | |||||
Radiated
Electromagnetic Field |
Conforms to EN61000-4-3 | ||||||
Electrical Fast
Transient/Burst |
Conforms to EN61000-4-4 | ||||||
Surge | Conforms to EN61000-4-5 | ||||||
Conducted
Disturbance |
Conforms to EN61000-4-6 | ||||||
Voltage Dips/Short
Interruptions |
Conforms to EN61000-4-11 | ||||||
Approved standards | UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No. 60950-1 EN: EN50178, EN60950-1 |
||||||
SEMI | SEMI F47-0706 (at 200 VAC) | ||||||
Weight *5 | 70 g max. (without chassis and cover) |
Power ratings | 30 W | |||||||
---|---|---|---|---|---|---|---|---|
Output voltage | 5 V | 12 V | 15 V | 24 V | 48 V | |||
Efficiency (Typ.) | 100 VAC input | 77% | 82% | 83% | 85% | 85% | ||
200 VAC input | 79% | 83% | 83% | 86% | 86% | |||
Input | Voltage *1 | 100 to 240 VAC (allowable voltage: 85 to 264 VAC, 120 to 370
VDC *6) |
||||||
Frequency *1 | 50/60 Hz (47 to 450 Hz) | |||||||
Current (Typ.) | 100 VAC input | 0.7 A | ||||||
200 VAC input | 0.4 A | |||||||
Leakage
current |
100 VAC input | 0.5 mA max. | ||||||
200 VAC input | 1mA max. | |||||||
Inrush current
(Typ.) |
100 VAC input | 15 A (for a cold start at 25°C) | ||||||
200 VAC input | 30 A (for a cold start at 25°C) | |||||||
Output | Voltage adjustment range *2 | ±10% (with V. ADJ) | ||||||
Ripple *3 | 150 mV max. | 240 mV
max. |
300 mV
max. |
480 mV
max. |
960 mV
max. |
|||
Input variation influence | 0.5% max. (with 85 to 264 VAC input at 100% load) | |||||||
Load variation influence | 2% max. (0
to 100% load, rated input voltage) |
1.5% max. (0 to 100% load, rated input voltage) | ||||||
Temperature variation influence | 0.05%/°C max. | |||||||
Startup time
(Typ.) |
100 VAC input | 800 ms | ||||||
Hold time (Typ.) | 100 VAC input | 20 ms | ||||||
Addi-
tional func- tions |
Overload protection | 105% to 160% of rated current, voltage drop, intermittent,
automatic reset |
||||||
Overvoltage protection *4 | Yes | |||||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||||||
Parallel operation | No (However, backup operation is possible; external diodes
required.) |
|||||||
Other | Ambient operating temperature | -10 to 70°C (Derating is required according to the temperature.)
(with no icing or condensation) |
||||||
Storage temperature | -25 to 75°C (with no icing or condensation) | |||||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||||||
Dielectric strength | 3.0 kVAC for 1 min.
(between all inputs and outputs; Cutoff current: 10 mA) 2.0 kVAC for 1 min. (between all inputs and PE; Cutoff current: 10 mA) 1.0 kVAC for 1 min. (between all outputs and PE; Cutoff current: 20 mA) |
|||||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminal) at
500 VDC |
|||||||
Vibration resistance | 10 to 55 Hz, 19.6 m/s2 (2 G) for 1 h each in X, Y, and Z directions | |||||||
Shock resistance | 196.1 m/s2, 3 times each in ±X, ±Y, ±Z directions | |||||||
EMI | Conducted Emissions | Conforms to EN 55011 Group 1 Class B *7 | ||||||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *7 | |||||||
EMS | Electrostatic
Discharge |
Conforms to EN61000-4-2 | ||||||
Radiated
Electromagnetic Field |
Conforms to EN61000-4-3 | |||||||
Electrical Fast
Transient/Burst |
Conforms to EN61000-4-4 | |||||||
Surge | Conforms to EN61000-4-5 | |||||||
Conducted
Disturbance |
Conforms to EN61000-4-6 | |||||||
Voltage Dips/Short
Interruptions |
Conforms to EN61000-4-11 | |||||||
Approved standards | UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No. 60950-1 EN: EN50178, EN60950-1 |
|||||||
SEMI | SEMI F47-0706 (at 200 VAC) | |||||||
Weight *5 | 110 g max. (without chassis and cover) |
Power ratings | 50 W | |||||
---|---|---|---|---|---|---|
Output voltage | 5 V | 12 V | 24 V | 48 V | ||
Efficiency (Typ.) | 100 VAC input | 79% | 83% | 82% | 82% | |
200 VAC input | 81% | 86% | 85% | 85% | ||
Input | Voltage *1 | 100 to 240 VAC (allowable voltage: 85 to 264 VAC, 120 to 370
VDC *6) |
||||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | |||||
Current (Typ.) | 100 VAC input | 0.65 A | ||||
200 VAC input | 0.35 A | |||||
Power factor (rate, 100% load) | 0.9 min. | |||||
Harmonic current emissions | Conforms to EN 61000-3-2 Class A. | |||||
Leakage
current |
100 VAC input | 0.5 mA max. | ||||
200 VAC input | 1 mA max. | |||||
Inrush current
(Typ.) |
100 VAC input | 14.1 A (for a cold start at 25°C) | ||||
200 VAC input | 28.3 A (for a cold start at 25°C) | |||||
Output | Voltage adjustment range *2 | ± 10% (with V. ADJ) | ||||
Ripple *3 | 150 mV max. | 240 mV max. | 480 mV max. | 960 mV max. | ||
Input variation influence | 0.5% max. (with 85 to 264 VAC input at 100% load) | |||||
Load variation influence | 2% max. (0 to
100% load, rated input voltage) |
1.5% max. (0 to 100% load, rated input voltage) | ||||
Temperature variation influence | 0.05%/ °C max. | |||||
Startup time
(Typ.) |
100 VAC input | 440 ms | 460 ms | 500 ms | 460 ms | |
Hold time (Typ.) | 100 VAC input | 25 ms | 20 ms | 23 ms | 22 ms | |
Addi-
tional func- tions |
Overload protection | 100% to 110% of rated load current, voltage drop, intermittent,
automatic reset |
||||
Overvoltage protection *4 | Yes | |||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||||
Parallel operation | No (However, backup operation is possible; external diodes
required.) |
|||||
Remote control | Yes (Only for models with remote control option.) | |||||
Other | Ambient operating temperature | -10 to 70 °C (Derating is required according to the
temperature.) (with no icing or condensation) |
||||
Storage temperature | -25 to 75 °C (with no icing or condensation) | |||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||||
Dielectric strength | 3.0 kVAC for 1 min.
(between all inputs and outputs; Cutoff current: 10 mA) 2.0 kVAC for 1 min. (between all inputs and PE; Cutoff current: 10 mA) 1.0 kVAC for 1 min. (between all outputs and PE; Cutoff current: 20 mA) |
|||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminal) at
500 VDC |
|||||
Vibration resistance | 10 to 55 Hz, 19.6 m/s2 (2 G) for 1 h each in X, Y, and Z directions | |||||
Shock resistance | 196.1 m/s2 , 3 times each in ± X, ± Y, ± Z directions | |||||
EMI | Conducted Emissions | Conforms to EN 55011 Group 1 Class B *7 | ||||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *7 | |||||
EMS | Electrostatic
Discharge |
Conforms to EN61000-4-2 | ||||
Radiated
Electromagnetic Field |
Conforms to EN61000-4-3 | |||||
Electrical Fast
Transient/Burst |
Conforms to EN61000-4-4 | |||||
Surge | Conforms to EN61000-4-5 | |||||
Conducted
Disturbance |
Conforms to EN61000-4-6 | |||||
Voltage Dips/Short
Interruptions |
Conforms to EN61000-4-11 | |||||
Approved standards | UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No. 60950-1 EN: EN50178, EN60950-1 |
|||||
SEMI | SEMI F47-0706 (at 200 VAC) | |||||
Weight *5 | 150 g max. (without chassis and cover) |
Power ratings | 100 W | |||||
---|---|---|---|---|---|---|
Output voltage | 5 V | 12 V | 24 V | 48 V | ||
Efficiency (Typ.) | 100 VAC input | 81% | 82% | 84% | 84% | |
200 VAC input | 84% | 85% | 86% | 86% | ||
Input | Voltage *1 | 100 to 240 VAC (allowable voltage: 85 to 264 VAC, 120 to 370
VDC *6) |
||||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | |||||
Current (Typ.) | 100 VAC input | 1.3 A | ||||
200 VAC input | 0.65 A | |||||
Power factor (rate, 100% load) | 0.9 min. | |||||
Harmonic current emissions | Conforms to EN 61000-3-2 Class A. | |||||
Leakage
current |
100 VAC input | 0.5 mA max. | ||||
200 VAC input | 1 mA max. | |||||
Inrush current
(Typ.) |
100 VAC input | 14.1 A (for a cold start at 25°C) | ||||
200 VAC input | 28.3 A (for a cold start at 25°C) | |||||
Output | Voltage adjustment range *2 | ± 10% (with V. ADJ) | ||||
Ripple *3 | 150 mV max. | 240 mV max. | 480 mV max. | 960 mV max. | ||
Input variation influence | 0.5% max. (with 85 to 264 VAC input at 100% load) | |||||
Load variation influence | 2% max. (0
to 100% load, rated input voltage) |
1.5% max. (0 to 100% load, rated input voltage) | ||||
Temperature variation influence | 0.05%/ °C max. | |||||
Startup time
(Typ.) |
100 VAC input | 480 ms | 530 ms | 540 ms | 650 ms | |
Hold time (Typ.) | 100 VAC input | 24 ms | 21 ms | 22 ms | 24 ms | |
Addi-
tional func- tions |
Overload protection | 12-V, 24-V, or 48-V model: 100% to 110% of power boost for output
current, voltage drop, intermittent, automatic reset 5-V model: 105% to 160% of rated current, voltage drop, intermittent, automatic reset |
||||
Overvoltage protection *4 | Yes | |||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||||
Parallel operation | No (However, backup operation is possible; external diodes required.) | |||||
Remote control | Yes (Only for models with remote control option.) | |||||
Other | Ambient operating temperature | -10 to 70 °C (Derating is required according to the temperature.)
(with no icing or condensation) |
||||
Storage temperature | -25 to 75 °C (with no icing or condensation) | |||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||||
Dielectric strength | 3.0 kVAC for 1 min.
(between all inputs and outputs; Cutoff current: 10 mA) 2.0 kVAC for 1 min. (between all inputs and PE; Cutoff current: 10 mA) 1.0 kVAC for 1 min. (between all outputs and PE; Cutoff current: 20 mA) |
|||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminal) at
500 VDC |
|||||
Vibration resistance | 10 to 55 Hz, 19.6 m/s2 (2 G) for 1 h each in X, Y, and Z directions | |||||
Shock resistance | 196.1 m/s2 , 3 times each in ± X, ± Y, ± Z directions | |||||
EMI | Conducted Emissions | Conforms to EN 55011 Group 1 Class B *7 | ||||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *7 | |||||
EMS | Electrostatic
Discharge |
Conforms to EN61000-4-2 | ||||
Radiated
Electromagnetic Field |
Conforms to EN61000-4-3 | |||||
Electrical Fast
Transient/Burst |
Conforms to EN61000-4-4 | |||||
Surge | Conforms to EN61000-4-5 | |||||
Conducted
Disturbance |
Conforms to EN61000-4-6 | |||||
Voltage Dips/Short
Interruptions |
Conforms to EN61000-4-11 | |||||
Approved standards | UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No. 60950-1 EN: EN50178, EN60950-1 |
|||||
SEMI | SEMI F47-0706 (at 200 VAC) | |||||
Weight *5 | 265 g max. (without chassis and cover) |
Power ratings | 150 W | |||||
---|---|---|---|---|---|---|
Output voltage | 5 V | 12 V | 24 V | 48 V | ||
Efficiency (Typ.) | 100 VAC input | 84% | 83% | 84% | 85% | |
200 VAC input | 87% | 86% | 87% | 88% | ||
Input | Voltage *1 | 100 to 240 VAC (allowable voltage: 85 to 264 VAC, 120 to 370
VDC *6) |
||||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | |||||
Current (Typ.) | 100 VAC input | 1.9 A | ||||
200 VAC input | 0.95 A | |||||
Power factor (rate, 100% load) | 0.9 min. | |||||
Harmonic current emissions | Conforms to EN 61000-3-2 Class A. | |||||
Leakage
current |
100 VAC input | 0.5 mA max. | ||||
200 VAC input | 1 mA max. | |||||
Inrush current
(Typ.) |
100 VAC input | 14.1 A (for a cold start at 25°C) | ||||
200 VAC input | 28.3 A (for a cold start at 25°C) | |||||
Output | Voltage adjustment range *2 | ± 10% (with V. ADJ) | ||||
Ripple *3 | 150 mV max. | 240 mV max. | 480 mV max. | 960 mV max. | ||
Input variation influence | 0.5% max. (with 85 to 264 VAC input at 100% load) | |||||
Load variation influence | 2% max. (0 to
100% load, rated input voltage) |
1.5% max. (0 to 100% load, rated input voltage) | ||||
Temperature variation influence | 0.05%/ °C max. | |||||
Startup time
(Typ.) |
100 VAC input | 450 ms | 660 ms | 660 ms | 690 ms | |
Hold time (Typ.) | 100 VAC input | 25 ms | 20 ms | 21 ms | 20 ms | |
Addi-
tional func- tions |
Overload protection | 12-V, 24-V, or 48-V model: 100% to 110% of power boost for output
current, voltage drop, intermittent, automatic reset 5-V model: 105% to 160% of rated current, voltage drop, intermittent, automatic reset |
||||
Overvoltage protection *4 | Yes | |||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||||
Parallel operation | No (However, backup operation is possible; external diodes required.) | |||||
Remote control | Yes (Only for models with remote control option.) | |||||
Other | Ambient operating temperature | -10 to 70 °C (Derating is required according to the temperature.)
(with no icing or condensation) |
||||
Storage temperature | -25 to 75 °C (with no icing or condensation) | |||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||||
Dielectric strength | 3.0 kVAC for 1 min.
(between all inputs and outputs; Cutoff current: 10 mA) 2.0 kVAC for 1 min. (between all inputs and PE; Cutoff current: 10 mA) 1.0 kVAC for 1 min. (between all outputs and PE; Cutoff current: 20 mA) |
|||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminal) at
500 VDC |
|||||
Vibration resistance | 10 to 55 Hz, 19.6 m/s2 (2 G) for 1 h each in X, Y, and Z directions | |||||
Shock resistance | 196.1 m/s2 , 3 times each in ± X, ± Y, ± Z directions | |||||
EMI | Conducted Emissions | Conforms to EN 55011 Group 1 Class B *7 | ||||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *7 | |||||
EMS | Electrostatic
Discharge |
Conforms to EN61000-4-2 | ||||
Radiated
Electromagnetic Field |
Conforms to EN61000-4-3 | |||||
Electrical Fast
Transient/Burst |
Conforms to EN61000-4-4 | |||||
Surge | Conforms to EN61000-4-5 | |||||
Conducted
Disturbance |
Conforms to EN61000-4-6 | |||||
Voltage Dips/Short
Interruptions |
Conforms to EN61000-4-11 | |||||
Approved standards | UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No. 60950-1 EN: EN50178, EN60950-1 |
|||||
SEMI | SEMI F47-0706 (at 200 VAC) | |||||
Weight *5 | 315 g max. (without chassis and cover) |
Power ratings | 240 W (300 W) | ||||
---|---|---|---|---|---|
Output voltage | 24 V | 36 V | 48 V | ||
Efficiency (Typ.) | 100 VAC input | 87% | 87% | 87% | |
200 VAC input | 90% | 90% | 90% | ||
Input | Voltage *1 | 100 to 240 VAC (allowable voltage: 85 to 264 VAC, 120 to 370
VDC *6) |
|||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | ||||
Current (Typ.) | 100 VAC input | 2.9 A (for 240-W output) | |||
200 VAC input | 1.5 A (for 240-W output)
1.8 A (for 300-W output) |
||||
Power factor (rate, 100% load) | 0.9 min. | ||||
Harmonic current emissions | Conforms to EN 61000-3-2 Class A. | ||||
Leakage
current |
100 VAC input | 0.5 mA max. | |||
200 VAC input | 1.0 mA max. | ||||
Inrush current
(Typ.) |
100 VAC input | 14 A (for a cold start at 25°C) | |||
200 VAC input | 28 A (for a cold start at 25°C) | ||||
Output | Voltage adjustment range *2 | ± 10% (with V. ADJ) | |||
Ripple *3 | 480 mV max. | 720 mV max. | 960 mV max. | ||
Input variation influence | 0.5% max. | ||||
Load variation influence | 1.5% max. | ||||
Temperature variation influence | 0.05%/ °C max. | ||||
Startup time
(Typ.) |
100 VAC input | 460 ms | |||
200 VAC input | 330 ms | ||||
Hold time (Typ.) | 100 VAC input | 20 ms (for output power of 240 W) | |||
200 VAC input | 20 ms (for output power of 240 W)
16 ms (for output power of 300 W) |
||||
Addi-
tional func- tions |
Overload protection *4 | 100% or higher of power boost for output current, voltage drop,
automatic reset Power shut off if 130% or higher of rated output current continues for approx. 5 s Reset by input reset (OFF time: 3 min min.) |
|||
Overvoltage protection *4 | Yes | ||||
Series operation | Yes (For up to two Power Supplies; external diodes are required.) | ||||
Parallel operation | No (However, backup operation is possible; external diodes required.) | ||||
Remote control | Yes (Only for models with remote control option.) | ||||
Undervoltage alarm output | Yes (open-collector output, 30 VDC max., 50 mA max.) | ||||
Other | Ambient operating temperature | -10 to 70 °C (Derating is required according to the temperature.)
(with no icing or condensation) |
|||
Storage temperature | -25 to 75 °C (with no icing or condensation) | ||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | ||||
Dielectric strength | 3.0 kVAC for 1 min.
(between all inputs and outputs; Cutoff current: 10 mA) 2.0 kVAC for 1 min. (between all inputs and PE; Cutoff current: 10 mA) 1.0 kVAC for 1 min. (between all outputs and PE; Cutoff current: 20 mA) |
||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminal) at 500
VDC (at room temperature 25°C and humidity 60%) |
||||
Vibration resistance | No abnormality after 10 to 55 Hz, 19.6 m/s2 (2 G) for 1 h each in X,
Y, and Z directions. |
||||
Shock resistance | 196.1 m/s2 , 3 times each in ± X, ± Y, ± Z directions | ||||
EMI | Conducted Emissions | Conforms to EN 55011 Group 1 Class B *7 | |||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *7 *8 | ||||
EMS | Electrostatic
Discharge |
Conforms to EN61000-4-2 | |||
Radiated
Electromagnetic Field |
Conforms to EN61000-4-3 | ||||
Electrical Fast
Transient/Burst |
Conforms to EN61000-4-4 | ||||
Surge | Conforms to EN61000-4-5 | ||||
Conducted
Disturbance |
Conforms to EN61000-4-6 | ||||
Voltage Dips/Short
Interruptions |
Conforms to EN61000-4-11 | ||||
Approved standards | UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No. 60950-1 EN: EN50178, EN60950-1 |
||||
SEMI | SEMI F47-0706 (at 200 VAC) | ||||
Weight *5 | 515 g (without chassis and cover) |
last update: April 2, 2018