Discontinued On Aug. 2022

CPM2C-S1[]0C

CPU Units with CompoBus/S Master

CPM2C-S1[]0C

Ultra-compact, Thin-profile CPM2C CPU Unit with CompoBus/S Master Offering High-speed Bus Communications with No Complicated Wiring

* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.

General Specifications

Item Specification
Control method Stored program method
I/O control method Cyclic scan method
(Immediate refreshing can be performed with IORF(97).)
Programming language Ladder diagram
Instruction length 1 step per instruction
1 to 5 words per instruction
Instructions Basic instructions 14
Special instructions 105 instructions, 185 variations
Execution
time
Basic instructions 0.64 μs (LD instruction)
Special instructions 7.8 μs (MOV instruction)
Program capacity 4,096 words
Max. I/O capacity CPU Unit only: 10 points
Expansion I/O Unit: 96 points (32-point Expansion I/O Unit x 3)
(Up to 3 Expansion Units can be connected.)
CompoBus/S: 256 points (362 points in total)
Input bits IR 00000 to IR 00915
(Bits not used for input bits can be used for work bits.)
Output bits IR 01000 to IR 01915
(Bits not used for output bits can be used for work bits.)
CompoBus/S input bits 128 bits: IR 02000 to IR 02715 (words IR 020 to IR 027)
CompoBus/S output bits 128 bits: IR 03000 to IR 03715 (words IR 030 to IR 037)
Work bits 672 bits:
IR 02800 to IR 02915 (words IR 028 to IR 029)
IR 03800 to IR 03915 (words IR 038 to IR 039)
IR 04000 to IR 04915 (words IR 040 to IR 049)
IR 20000 to IR 22715 (words IR 200 to IR 227)
Special bits (SR area) 440 bits: SR 22800 to SR 25507 (words SR 228 to SR 255)
Temporary bits (TR area) 8 bits: (TR 0 to TR 7)
Holding bits (HR area) 320 bits: HR 0000 to HR 1915 (words HR 00 to HR 19)
Auxiliary bits (AR area) 384 bits: AR 0000 to AR 2315 (words AR 00 to AR 23)
These include CompoBus/S slave status flags (words AR 04 to AR 07).
Link bits (LR area) 256 points: LR 0000 to LR 1515 (words LR 00 to LR 15)
Timers/Counters 256 timers/counters: TIM/CNT 000 to TIM/CNT 255
1-ms timers: TMHH (--)
10-ms timers: TIMH (15)
100-ms timers TIM
1-s/10-s timers: TIML (--)
Decrementing counters: CNT
Reversible counters: CNTR (12)
Data memory Read/Write 2,048 words (DM 0000 to DM 2047)
The Error Log is contained in DM 2000 to DM 2021.
Read only 456 words (DM 6144 to DM 6599)
PC Setup 56 words (DM 6600 to DM 6655)
Basic
interrupt
functions
Interrupt inputs 2 interrupts (Used for both counter mode interrupts inputs and quick-
response inputs.
Scheduled interrupts 1 interrupt
High-speed
counter
functions
High-speed counters 1 counter (single phase at 20 kHz or 2 phases at 5 kHz)
Counter
interrupts
1 interrupt (set value comparison or set-value range comparison)
Interrupt inputs
(counter mode)
2 interrupts (Used for both external interrupts inputs and quick-response
inputs.)
Count-up
interrupts
2 interrupts (Used for both external interrupts inputs and quick-response
inputs.)
Quick-response inputs 2 points (Used for both external interrupts inputs and counter mode
interrupt inputs.)
Min. input pulse width: 50 μs max.
Pulse output 2 points with no acceleration/deceleration,
10 Hz to 10 kHz each, and no direction control: 1 point with trapezoid
acceleration/deceleration,
10 Hz to 10 kHz with direction control: or 2 points with variable duty-ratio
outputs
Synchronized pulse control 1 point
Input time constant
(ON response time = OFF response
time)
Can be set for CPU Unit inputs and Expansion Unit inputs only
(1, 2, 3, 5, 10, 20, 40, or 80 ms)
Clock Equipped with clock (built-in RTC)
Communications functions Peripheral port: Supports Host Link, peripheral bus, no-protocol
communications, and Programming Console connections.
RS-232C port: Supports Host Link, no-protocol communications, 1-to-1
Link, or 1-to-1 NT Link connections.
Power failure backup function Data in HR, AR, Counter (CNT), and Data Memory (DM) areas is held.
Memory backup Non-volatile (flash) memory: Program, read-only DM area, and PC Setup
Memory backup (lithium battery: 2 years lifetime): DM area, HR area, AR area,
and counter values
Self-diagnostic functions CPU error (watchdog timer), memory errors, communications errors, setting
errors, battery errors, and expansion I/O bus errors
Program check No END instruction, programming errors (checked when operation is started)
Programming
devices
Programming Console C200H-PRO27, CQM1-PRO01, or CQM1H-PRO01
SSS IBM PC/AT or compatible (SYSMAC Support Software version 1.1 or higher)
CPT Windows
CX-P Windows

Note: Connecting Cable (CPM2C-CN111, CS1W-CN114, or CS1W-CN118) is required to connect to the communications
          peripheral/RS-232C port.

Communications Specifications

Communications method Special CompoBus/S protocol
Coding method Manchester coding
Connection form Combination of multi-drop method and T-branch connections *1
Baud rate High-speed Communications Mode: 750 kbps
Long-distance Communications Mode: 93.75 kbps *2
Commu-
nications
cycle time
cycle time
High-speed
Communications Mode
0.5 ms (with 8 input and 8 output slaves connected)
0.8 ms (with 16 input and 16 output slaves connected)
Long-distance
Communications Mode
4.0 ms (with 8 input and 8 output slaves connected)
6.0 ms (with 16 input and 16 output slaves connected)
Communications media 2-conductor cable (VCTF 0.75 x 2), 4-conductor cable (VCTF 0.75 x 4),
or Special Flat Cable
Commu-
nications
distance
High-speed
Communications Mode
2-conductor VCTF cable:
Main line length: 100 m max.
Branch line length: 3 m max.
Total branch line length: 50 m max.
Special Flat Cable, 4-conductor VCTF cable:
Main line length: 30 m max.
Branch line length: 3 m max.
Total branch line length: 30 m max.
(When Special Flat Cable is used to connect fewer than 16 Slaves, the main line
can be up to 100 m long and the total branch line length can be up to 50 m.)
Long-distance
Communications Mode
2-conductor VCTF cable:
Main line length: 500 m max.
Branch line length: 6 m max.
Total branch line length: 120 m max.
Special Flat Cable, 4-conductor VCTF cable:
Variable branch wiring (total cable length 200 m max.)
(There are no limits on the branching format or main, branch, or total line
lengths. The terminator must be connected to the point in the system farthest
from the master.)
Maximum number of nodes 32
Error control checks Manchester code check, frame length check, and parity check

*1. A terminator must be connected to the point in the system farthest from the Master.
*2. The baud rate is switched using DM settings (default setting is 750 kbps).