SmartSlice
last update: February 6, 2014
|
Common SmartSlice Specifications
|
|
|---|---|
| Unit power supply voltage | 24 VDC (20.4 to 26.4 VDC) |
| I/O power supply voltage | 24 VDC (20.4 to 26.4 VDC) |
| I/O connection | Screwless push-in technology |
| Noise immunity | Conforms to IEC61000-4-4, 2.0 kV (power supply line) |
| Vibration resistance | 10 to 60 Hz: 0.7 mm double amplitude 60 to 150 Hz: 50 m/s2 |
| Shock resistance | 150 m/s2, 3 times in each direction |
| Dielectric strength | 500 VAC (between isolated circuits) |
| Insulation resistance | 20 MΩ min. (between isolated circuits) |
| Ambient operating temperature | -10 to 55°C (with no icing or condensation) |
| Ambient operating humidity | 25% to 85% |
| Operating environment | No corrosive gases |
| Ambient storage temperature | -25 to 65°C (with no icing or condensation) |
| Mounting | 35 mm DIN rail |
|
Model name
|
GRT1-PRT
|
|---|---|
| Network Specification | PROFIBUS-DPV1 |
| Network connector | 9-pin D-Sub |
| Network interface power supply | Internal |
| Number of I/O points | 1,024 inputs and outputs max. (128 bytes each) |
| Number of connectable Units | 64 SmartSlice I/O Units max. |
| I/O power supply | 24 VDC, 4 A max. |
| Status flags | 1 word for Communications Unit status flags |
| Parameter backup and restore | up to 2 KB of data per I/O Unit. |
last update: February 6, 2014