Conductive Level Controller
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: February 28, 2013
| Rated voltage | 24 VAC, 50/60 Hz, or 24 VDC
100 to 240 VAC, 50/60 Hz |
|---|---|
| Operating voltage range | 85% to 110% of rated voltage |
| Voltage between
electrodes |
6 V p-p (approx. 20 Hz) |
| Power consumption | 24 VDC: 2 W max.
24 VAC: 4 VA max. 100 to 240 VAC: 5 VA max. |
| Operating resistance | 10 kΩ to 100 kΩ (variable) |
| Reset resistance | 250 kΩ max. |
| Response time | Approx. 0.1 to 10 s (variable) |
| Cable length | 100 m max. with completely insulated (600 V) cabtire cable with 3 conductors (0.75 mm2) |
| Control output | 6 A at 250 VAC for resistive load at 20°C, 1 A at 250 VAC for inductive load cosφ = 0.4
at 20°C |
| Indicators | Green LED: Power, Yellow LED: Control output |
| Ambient temperature | Operating: -20 to 60°C, Storage: -30 to 70°C (with no condensation or icing) |
| Ambient humidity | Operating: 25% to 85%, Storage: 25% to 85% |
| Elevation | 2,000 m max. |
| Insulation resistance | 100 MΩ min. (at 500 VDC) between power supply section, electrode section, and contact
section |
| Dielectric strength | 2,000 VAC 50/60 Hz for 1 min between power source section, electrode section, and
contact section |
| Vibration resistance | Vibration of 10 to 55 Hz and acceleration of 50 m/s2 for 5 min. 10 times each in X, Y, and
Z directions |
| Shock resistance | 100 m/s2 3 times each in 6 directions on 3 axes |
| Installation environment | Overvoltage Category II, Pollution Degree 2 |
| Safety standards | EN61010-1 |
| EMC | EN61326 Industrial applications |
last update: February 28, 2013