Digital Timer
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: November 24, 2020
| Models | H5CZ-L8[] | ||
|---|---|---|---|
| Ratings | Power supply
voltage *1 |
100 to 240 VAC 50/60 Hz
12 to 24 VDC/24 VAC 50/60 Hz |
|
| Operating voltage
fluctuation range |
85% to 110% of rated supply voltage (90% to 110% at 12 to 24 VDC) | ||
| Power consumption | Approx. 6.2 VA at 100 to 240 VAC, Approx. 5.1 VA/2.4 W at 24 VAC/12 to 24 VDC *2 | ||
| Mounting method | Flush mounting, Surface mounting, DIN track mounting | ||
| External connections | 8-pin socket | ||
| Degree of protection | IEC IP66, UL508 Type 4X (indoors) for panel surface only and when Y92S-29
Waterproof Packing is used 4 digits |
||
| Digits | |||
| Time ranges | 0.001 s to 9.999 s, 0.01 s to 99.99 s, 0.1 s to 999.9 s, 1 s to 9999 s, 1 s to 99 min
59 s 0.1 m to 999.9 min, 1 min to 9999 min, 1 min to 99 h 59 min, 0.1 h to 999.9 h, 1 h to 9999 h |
||
| Timer mode | Elapsed time (Up), Remaining time (Down) (selectable) | ||
| Inputs | Input signals | Signal, Reset
(no inputs on models with instantaneous contact outputs) |
|
| Input method | No-voltage Input
ON impedance: 1 kΩ max. (Leakage current: 12 mA when 0 Ω ) ON residual voltage: 3 V max. OFF impedance: 100 kΩ min. |
||
| Signal, reset | Minimum input signal width: 1 or 20 ms (selectable, same for all input) | ||
| Reset system | Power reset (depending on output mode), External reset, Manual reset, Automatic
reset (depending on output mode) |
||
| Power reset | Minimum power-opening time: 0.5 s (except for A-3, b-1, F, ton-1, and toff-1
mode) |
||
| Reset voltage | 10% max. of rated supply voltage | ||
| Sensor waiting time | 250 ms max. (Control output is turned OFF and no input is accepted during sensor
waiting time.) |
||
| Output | Output modes | A: Signal ON Delay I, A-1: Signal ON Delay
II, A-2: Power ON Delay I, A-3: Power ON Delay II, b: Repeat Cycle 1, b-1: Repeat Cycle 2, d: Signal OFF Delay, E: Interval, F: Cumulative, Z: ON/OFF-duty-adjustable flicker, S: Stopwatch, toff: Flicker OFF Start 1, ton: Flicker ON Start 1, toff-1: Flicker OFF Start 2, ton-1: Flicker ON Start 2 |
|
| Models with Instantaneous Contact
Outputs A-2: Power ON Delay I, b: Repeat Cycle 1, E: Interval, Z: ON/OFF-duty- adjustable flicker, toff: Flicker OFF Start 1, ton: Flicker ON Start 1 |
|||
| One-shot output time | 0.01 to 99.99 s | ||
| Control output | 5 A at 250 VAC/30 VDC, resistive load (cos =1)
Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value) Contact materials: AgSnIn |
||
| Display method *3 | LCD; Present value: 10-mm-high characters
Set value: 6-mm-high characters |
||
| Memory backup | EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min. | ||
| Operating temperature range | -10 to 55°C (-10 to 50°C if counters are mounted side by side) (with no icing or
condensation) |
||
| Storage temperature range | -25 to 70°C (with no icing or condensation) | ||
| Operating humidity range | 25% to 85% | ||
| Front panel color | Light gray (5Y7/1) | ||
| Voltage | Applied voltage | Inrush current (peak value) | Time |
|---|---|---|---|
| 100 to 240 VAC | 264 VAC | 5.3 A | 0.4 ms |
| 12 to 24 VDC/24 VAC | 26.4 VAC | 6.4 A | 1.4 ms |
| 26.4 VDC | 4.4 A | 1.7 ms |
*3. The display is lit only when the power is ON. Settings and changes are not possible if the power supply is not ON.
| Accuracy of operating
time and setting error (including temperature and voltage influences) |
Power-ON start: ±0.01% ±50 ms max. *1
Signal start: ±0.005%±0.03 ms max. *1 If the set value is within the sensor waiting time at startup the control output of the H5CZ will not turn ON until the sensor waiting time passes. |
|
|---|---|---|
| Insulation resistance | 100 MΩ min. (at 500 VDC) between current-carrying terminal and exposed non-current-carrying metal parts, and between non-continuous contacts | |
| Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts
2,000 VAC, 50/60 Hz for 1 min between power supply and input circuits (H5CZ-L8 only) 2,000 VAC, 50/60 Hz for 1 min between control output, power supply, and input circuits (for all models except H5CZ-L8E[]) 1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts |
|
| Impulse withstand voltage | 5 kV (between power terminals) for 100 to 240 VAC, 1 kV for 24 VAC/12 to 24 VDC
5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC 1.5 kV for 24 VAC/12 to 24 VDC |
|
| Noise immunity | ±1.5 kV (between power terminals) and ±600 V (between input terminals (for all models except H5CZ-L8E[])), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) | |
| Static immunity | Malfunction: 8 kV
Destruction: 15 kV |
|
| Vibration
resistance |
Destruction | 10 to 55 Hz with 0.75-mm single amplitude each in three directions for 2 h each |
| Malfunction | 10 to 55 Hz with 0.35-mm single amplitude each in three directions for 10 min each | |
| Shock
resistance |
Destruction | 300 m/s2 in three directions, three cycles |
| Malfunction | 100 m/s2 in three directions, three cycles | |
| Life
expectancy |
Mechanical | 10,000,000 operations min. (under no load at 1,800 operations/h and ambient
temperature of 23°C) |
| Electrical | 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h and
ambient temperature of 23°C) * 2 |
|
| Weight | Approx. 105 g (Timer only) | |
*1. The values are based on the set value.
*2. Refer to Life-test Curve.
A maximum current of 0.15 A can be switched at 125 VDC (cosφ =1) and a maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected.
| Approved safety standards | UL508/Listing, UL50 Type 4X for indoor use (enclosure rating), CSA C22.2 No. 14 *1,
conforms to EN61812-1 (Pollution degree 2/overvoltage category III) B300 PILOT DUTY 1/4 HP 120 VAC, 1/3 HP, 240 VAC, 5 A resistive load VDE0106/P100 CCC: GB/T 14048.5 Pollution degree 2, Overvoltage category III *2 |
|---|---|
| EMC | (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A Emission AC mains: EN55011 Group 1 class A (EMS) EN61812-1 Immunity ESD: IEC61000-4-2 Immunity RF-interference: IEC61000-4-3 Immunity Burst: IEC61000-4-4 Immunity Surge: IEC61000-4-5 Immunity Conducted Disturbance: IEC61000-4-6 Immunity Voltage Dip/Interruption: IEC61000-4-11 |
| Rated operating voltage Ue
Rated operating current Ie |
AC-15: Ue: 250 VAC, Ie: 3 A
AC-13: Ue: 250 VAC, Ie: 5 A DC-13: Ue: 30 VDC, Ie: 0.5 A |
|---|---|
| Rated insulation voltage | 250 V |
| Rated impulse withstand voltage
(altitude: 2,000 m max.) |
4 kV (at 240 VAC) |
| Conditional short-circuit current | 1000 A |
For details, refer to the timing charts on Data Sheet.
| Inputs * | Start signal | Normally functions to start timing.
In modes A-2 and A-3, disable timing. In mode S, starts and stops timing. |
|---|---|---|
| Reset | • Resets present value. (In elapsed time mode, the present value returns to 0; in remaining time
mode, the present value returns to the set value.) • Count inputs are not accepted and control output turns OFF while reset input is ON. • Reset indicator is lit while reset input is ON. |
|
| Outputs | Control output
(OUT) |
Outputs take place according to designated operating mode when timer reaches corresponding set value. |
* The H5CZ-L8E[] does not have an input.
last update: November 24, 2020