CompoNet Master Board for PCI Bus/CompactPCI Bus
            
        
last update: April 2, 2018
| Item | Specification | 
|---|---|
| Communications protocol | CompoNet Network protocol | 
| Types of communications | Remote I/O communications (programless, constant sharing of data with Slave Units)
 and message communications (explicit message communications as required with Slave Units and FINS message communications as required with controllers) *1  | 
								
| Baud rate | 4 Mbps *2, 3 Mbps, 1.5 Mbps, 93.75 kbps | 
| Modulation | Base-band | 
| Coding | Manchester code | 
| Error control | Manchester code rules, CRC | 
| Communications media *3 | The following media can be used.
 • Round cable I 2-wire 0.75 mm2 • Round cable II 4-wire 0.75 mm2 • Flat Cable I  | 
								
| Communications distance
 and wiring  | 
									Refer to Cable Types, Baud Rates, and Maximum Distances in the Master Unit
 Operation Manual.  | 
								
| Connectable Master Units | CompoNet Master Units | 
| Connectable Slave Units | CompoNet Slave Units | 
| Maximum I/O capacity | Word Slave Units: 1,024 inputs and 1,024 outputs (2,048 I/O points total)
 Bit Slave Units: 256 inputs and 256 outputs (512 I/O points total)  | 
								
| Maximum number of nodes | Word Slave Units: 64 input nodes and 64 output nodes
 Bit Slave Units: 128 input nodes and 128 output nodes Repeater Units: 64 nodes  | 
								
| Bits allocated per node
 address  | 
									Word Slave Units: 16 bits
 Bit Slave Units: 2 bits  | 
								
| Maximum number of nodes
 per trunk line or sub- trunk line  | 
									32 nodes (Slave Units and Repeater Units) | 
| Applicable node addresses | Word Slave Units: IN0 to IN63 and OUT0 to OUT63
 Bit Slave Units: IN0 to IN127 and OUT0 to OUT127 Repeater Units: 0 to 63  | 
								
| Repeater Unit application
 conditions  | 
									Up to 64 Repeater Units can be connected per network (i.e., per Master Unit). Up to 32
 Repeater Units can be connected per trunk line or per sub-trunk line. When Repeater Units are connected in series from the Master Unit, up to two extra segment layers can be created (i.e., up to 2 Repeater Units are allowed between a Slave Unit and the Master Unit).  | 
								
| Signal lines | Two lines: BDH (communications data high) and BDL (communications data low) | 
| Power lines | Two lines: BS+ and BS- (power for communications and internal Slave Unit circuits)
 • Power is supplied from the Master Unit or Repeater Units.  | 
								
| Communications power
 supply voltage  | 
									24 VDC ±10% | 
| Connection forms | Round cable II (4-wire) or Flat cable I at baud rate of 93.75 kbits/s: No restrictions
 Other cables or baud rates: Trunk line and branch lines  | 
								
| Connections for Slave Units and Repeater Units: T-branch or multidrop connections | 
| Item | Specifications | 
|---|---|
| 3G8F7-CRM21 (PCI) | |
| Bus specification | PCI bus Rev2.2
 5 V  | 
| Number of mountable boards | 4 pieces | 
| Compatible OS | Microsoft Windows 2000/XP (32 Bit version)/Vista (32 Bit version)/7 (32 Bit version)
 Other OS can be used, when the shared memory interface is directly accessed.  | 
| Weight | 90 g max. | 
| Operation voltage | Internal power supply: 5 VDC±5%
 3.3 VDC is not used.  | 
| Consumption current | Internal power supply: 5 VDC and 1.5 A max
 Communications power supply: 24 VDC and 80 mA max  | 
| Vibration resistance | 10 to 57 Hz, Amplitude 0.075 mm, 57 to 150 Hz
 Acceleration 9.8 m/s2, 80 min in each direction of X, Y and Z (8 min of each sweep time × 10 sweeps = total 80 min)  | 
| Shock resistance | 147 m/s2, 3 times in each direction of X, Y and Z. | 
| Ambient operating temperature | 0 to 55°C | 
| Ambient operating humidity | 0% to 80% RH (with no condensation) | 
| Ambient operating atmosphere | No corrosive gas | 
| Storage temperature | -20 to +60°C | 
            • Microsoft Visual C++ (Ver 6.0 to Ver 2008)
• Microsoft Visual Basic (Ver 6.0)
• CodeGear C++Builder (Ver 5 to Ver 2009)
        
last update: April 2, 2018