Solid State Contactors for Heaters
            
        
last update: September 24, 2012
UL508, CSA22.2 No.14, and EN60947-4-3
| Model | Same for all models | 
|---|---|
| Rated operating voltage | 12 to 24 VDC | 
| Operating voltage range | 9.6 to 30 VDC | 
| Rated input current (impedance) | 10 mA max. (24 VDC) | 
| Must-operate voltage | 9.6 VDC max. | 
| Must-release voltage | 1 VDC min. | 
| Insulation method | Phototriac | 
| Operation indicator | Yellow LED | 
| Model | G3PE-
 215B- 3(N)  | 
									G3PE-
 215B- 2(N)  | 
									G3PE-
 225B- 3(N)  | 
									G3PE-
 225B- 2(N)  | 
									G3PE-
 235B- 3(N)  | 
									G3PE-
 235B- 2(N)  | 
									G3PE-
 245B- 3(N)  | 
									G3PE-
 245B- 2(N)  | 
								
|---|---|---|---|---|---|---|---|---|
| Rated load voltage | 100 to 240 VAC | |||||||
| Operating voltage range | 75 to 264 VAC | |||||||
| Rated load current *1 | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
| Minimum load current | 0.2 A | 0.5 A | ||||||
| Inrush current resistance
 (peak value)  | 
									150 A
 (60 Hz, 1 cycle)  | 
									220 A
 (60 Hz, 1 cycle)  | 
									440 A
 (60 Hz, 1 cycle)  | 
								|||||
| Permissible I2t (reference value) | 121A2s | 260A2s | 1,260A2s | |||||
| Applicable load (resistive load:
 AC1 class) *2  | 
									5.1 kW
 (at 200 VAC)  | 
									8.6 kW
 (at 200 VAC)  | 
									12.1 kW
 (at 200 VAC)  | 
									15.5 kW
 (at 200 VAC)  | 
								||||
| Model | G3PE-
 515B- 3(N)  | 
									G3PE-
 515B- 2(N)  | 
									G3PE-
 525B- 3(N)  | 
									G3PE-
 525B- 2(N)  | 
									G3PE-
 535B- 3(N)  | 
									G3PE-
 535B- 2(N)  | 
									G3PE-
 545B- 3(N)  | 
									G3PE-
 545B- 2(N)  | 
								
|---|---|---|---|---|---|---|---|---|
| Rated load voltage | 200 to 480 VAC | |||||||
| Operating voltage range | 180 to 528 VAC | |||||||
| Rated load current *1 | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
| Minimum load current | 0.5 A | |||||||
| Inrush current resistance
 (peak value)  | 
									220 A
 (60 Hz, 1 cycle)  | 
									440 A
 (60 Hz, 1 cycle)  | 
								||||||
| Permissible I2t (reference value) | 260A2s | 1,260A2s | ||||||
| Applicable load (resistive load:
 AC1 class) *2  | 
									12.5 kW
 (at 480 VAC)  | 
									20.7 kW
 (at 480 VAC)  | 
									29.0 kW
 (at 480 VAC)  | 
									37.4 kW
 (at 480 VAC)  | 
								||||
       
    
| Model | G3PE-
 215B- 3H  | 
									G3PE-
 215B- 2H  | 
									G3PE-
 225B- 3HH  | 
									G3PE-
 225B- 2H  | 
									G3PE-
 235B- 3H  | 
									G3PE-
 235B- 2H  | 
									G3PE-
 245B- 3H  | 
									G3PE-
 245B- 2H  | 
								
|---|---|---|---|---|---|---|---|---|
| Rated load voltage | 100 to 240 VAC | |||||||
| Operating voltage range | 75 to 264 VAC | |||||||
| Rated load current * | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
| Minimum load current | 0.2 A | 0.5 A | ||||||
| Inrush current resistance
 (peak value)  | 
									150 A
 (60 Hz, 1 cycle)  | 
									220 A
 (60 Hz, 1 cycle)  | 
									440 A
 (60 Hz, 1 cycle)  | 
								|||||
| Permissible I2t (reference value) | 121A2s | 260A2s | 1,260A2s | |||||
| Applicable load (resistive load:
 AC1 class)  | 
									Refer to Engineering Data on Data Sheet. | |||||||
| Model | G3PE-
 515B- 3H  | 
									G3PE-
 515B- 2H  | 
									G3PE-
 525B- 3H  | 
									G3PE-
 525B- 2H  | 
									G3PE-
 535B- 3H  | 
									G3PE-
 535B- 2H  | 
									G3PE-
 545B- 3H  | 
									G3PE-
 545B- 2H  | 
								
|---|---|---|---|---|---|---|---|---|
| Rated load voltage | 200 to 480 VAC | |||||||
| Operating voltage range | 180 to 528 VAC | |||||||
| Rated load current * | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
| Minimum load current | 0.5 A | |||||||
| Inrush current resistance
 (peak value)  | 
									220 A
 (60 Hz, 1 cycle)  | 
									440 A
 (60 Hz, 1 cycle)  | 
								||||||
| Permissible I2t (reference value) | 260A2s | 1,260A2s | ||||||
| Applicable load (resistive load:
 AC1 class)  | 
									Refer to Engineering Data on Data Sheet. | |||||||
| Model | 
										G3PE- 215B- 3(N)  | 
									
										G3PE- 215B- 2(N)  | 
									
										G3PE- 225B- 3(N)  | 
									
										G3PE- 225B- 2(N)  | 
									
										G3PE- 235B- 3(N)  | 
									
										G3PE- 235B- 2(N)  | 
									
										G3PE- 245B- 3(N)  | 
									
										G3PE- 245B- 2(N)  | 
								
|---|---|---|---|---|---|---|---|---|
| Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
| Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
| 
										Output ON voltage drop  | 
									1.6 V (RMS) max. | |||||||
| Leakage current * | 10 mA max. (at 200 VAC) | |||||||
| 
										Insulation resistance  | 
									100 M Ω min. (at 500 VDC) | |||||||
| Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
| 
										Vibration resistance  | 
									DIN Track mounting: 10 to 55 to 10 Hz, 0.175-mm single amplitude (0.35-mm double amplitude) Screw mounting: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)  | 
								|||||||
| Shock resistance | 294 m/s2 (reverse mounting: 98 m/s2) | |||||||
| 
										Ambient storage temperature  | 
									- 30 to 100 ° C (with no icing or condensation) | |||||||
| 
										Ambient operating temperature  | 
									- 30 to 80 ° C (with no icing or condensation) | |||||||
| 
										Ambient operating humidity  | 
									45% to 85% | |||||||
| Weight | Approx. 1.25 kg | Approx. 1.45 kg  | 
									Approx. 1.25 kg  | 
									Approx. 1.65 kg  | 
									Approx. 1.45 kg  | 
									Approx. 2.0 kg  | 
									Approx. 1.65 kg  | 
								|
| Model | 
										G3PE- 515B- 3(N)  | 
									
										G3PE- 515B- 2(N)  | 
									
										G3PE- 525B- 3(N)  | 
									
										G3PE- 525B- 2(N)  | 
									
										G3PE- 535B- 3(N)  | 
									
										G3PE- 535B- 2(N)  | 
									
										G3PE- 545B- 3(N)  | 
									
										G3PE- 545B- 2(N)  | 
								
|---|---|---|---|---|---|---|---|---|
| Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
| Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
| 
										Output ON voltage drop  | 
									1.8 V (RMS) max. | |||||||
| Leakage current * | 20 mA max. (at 480 VAC) | |||||||
| 
										Insulation resistance  | 
									100 M Ω min. (at 500 VDC) | |||||||
| Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
| 
										Vibration resistance  | 
									DIN Track mounting: 10 to 55 to 10 Hz, 0.175-mm single amplitude (0.35-mm double amplitude) Screw mounting: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)  | 
								|||||||
| Shock resistance | 294 m/s2 (reverse mounting: 98 m/s2) | |||||||
| 
										Ambient storage temperature  | 
									- 30 to 100 ° C (with no icing or condensation) | |||||||
| 
										Ambient operating temperature  | 
									- 30 to 80 ° C (with no icing or condensation) | |||||||
| 
										Ambient operating humidity  | 
									45% to 85% | |||||||
| Weight | Approx. 1.25 kg | Approx. 1.45 kg  | 
									Approx. 1.25 kg  | 
									Approx. 1.65 kg  | 
									Approx. 1.45 kg  | 
									Approx. 2.0 kg  | 
									Approx. 1.65 kg  | 
								|
* The leakage current of phase S will be approximately √3 times larger if the 2-element model is used.
| Model | G3PE-
 215B- 3H  | 
									G3PE-
 215B- 2H  | 
									G3PE-
 225B- 3H  | 
									G3PE-
 225B- 2H  | 
									G3PE-
 235B- 3H  | 
									G3PE-
 235B- 2H  | 
									G3PE-
 245B- 3H  | 
									G3PE-
 245B- 2H  | 
								
|---|---|---|---|---|---|---|---|---|
| Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
| Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
| Output ON voltage drop | 1.6 V (RMS) max. | |||||||
| Leakage current * | 10 mA max. (at 200 VAC) | |||||||
| Insulation resistance | 100 M Ω min. (at 500 VDC) | |||||||
| Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
| Vibration resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | |||||||
| Shock resistance | Destruction: 294 m/s2 | |||||||
| Ambient storage temperature | - 30 to 100 ° C (with no icing or condensation) | |||||||
| Ambient operating temperature | - 30 to 80 ° C (with no icing or condensation) | |||||||
| Ambient operating humidity | 45% to 85% | |||||||
| Weight | Approx. 300 g | |||||||
| Model | G3PE-
 515B- 3H  | 
									G3PE-
 515B- 2H  | 
									G3PE-
 525B- 3H  | 
									G3PE-
 525B- 2H  | 
									G3PE-
 535B- 3H  | 
									G3PE-
 535B- 2H  | 
									G3PE-
 545B- 3H  | 
									G3PE-
 545B- 2H  | 
								
|---|---|---|---|---|---|---|---|---|
| Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
| Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
| Output ON voltage drop | 1.8 V (RMS) max. | |||||||
| Leakage current * | 20 mA max. (at 480 VAC) | |||||||
| Insulation resistance | 100 M Ω min. (at 500 VDC) | |||||||
| Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
| Vibration resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | |||||||
| Shock resistance | Destruction: 294 m/s2 | |||||||
| Ambient storage temperature | - 30 to 100 ° C (with no icing or condensation) | |||||||
| Ambient operating temperature | - 30 to 80 ° C (with no icing or condensation) | |||||||
| Ambient operating humidity | 45% to 85% | |||||||
| Weight | Approx. 300 g | |||||||
* The leakage current of phase S will be approximately √3 times larger if the 2-element model is used.
| Model | Weight | 
|---|---|
| Y92B-P50 | Approx. 450 g | 
| Y92B-P100 | Approx. 450 g | 
| Y92B-P150 | Approx. 600 g | 
| Y92B-P200 | Approx. 850 g | 
| Y92B-P250 | Approx. 1,200 g | 
last update: September 24, 2012