Low-speed Monitoring Unit
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: December 11, 2017
| Model | G9SX-LM224-[] | G9SX-EX401-[] |
|---|---|---|
| Rated supply voltage | 24 VDC | |
| Operating voltage range | -15% to +10% of rated supply voltage | |
| Power consumption * | 5 W max. | 2 W max. |
* Power consumption of loads not included.
| Model | G9SX-LM224-[] |
|---|---|
|
Safety input Enabling input Feedback/reset input Mode selector input |
Operating voltage: 20.4 VDC to 26.4 VDC Internal impedance: Approx. 2.8 kΩ * |
| Rotation detection input | Operating voltage: 20.4 VDC to 26.4 VDC Internal impedance: Approx. 2.8 kΩ * Frequency input range: 1 kHz max. |
* Provide a current equal to or higher than that of the minimum applicable load of the connected input control device.
| Model | G9SX-LM224-[] |
|---|---|
| Safety instantaneous output *1 | Source output (PNP compatible) Load current: 0.8 A DC max. * 2 |
| Safety speed detection output *1 | Source output (PNP compatible) Load current: 0.3 A DC max. |
| Auxiliary output | Source output (PNP compatible) Load current: 100 mA DC max. |
| Model | G9SX-EX-[] |
|---|---|
| Rated load | 250 VAC, 3A /30 VDC, 3A (resistive load) |
| Rated carry current | 3A |
| Maximum switching voltage | 250 VAC, 125 VDC |
| Model | G9SX-LM224 | G9SX-EX401 | |
|---|---|---|---|
|
Over-voltage category (IEC/EN60664-1) |
II | II (Safety relay outputs 13 to 43 and 14 to 44: III) | |
|
Operating time (OFF to ON state) *1 *2 *5 |
50 ms max. (Safety input: ON, Enabling input: ON) 100 ms max. (Logical AND connection input: ON) |
30 ms max. *6 | |
|
Response time (ON to OFF state) *1 *5 |
15 ms max. | 10 ms max. *6 | |
|
Allowable time for switching Mode selector inputs *3 |
450 ms max. | -- | |
|
Mode selector input response time *4 |
50 ms max. | -- | |
| ON-state residual voltage | 3.0 V max. (safety instantaneous outputs, safety speed detection outputs, and auxiliary outputs) | ||
| OFF-state leakage current | 0.1 mA max. (safety instantaneous outputs, safety speed detection outputs, and auxiliary outputs) | ||
|
Maximum cable length for logical connection inputs and Safety inputs |
100 m max. (External connection impedance: 100 Ω max. and 10 nF max.) | ||
| Reset input time | 100 ms min. | ||
|
Accuracy tolerance of low speed detection frequency |
Within minus 10% of the set value | -- | |
|
Insulation resistance |
Between logical AND connection terminals, and power supply input terminals and other input and output terminals connected together |
20 MΩ min., 250 VDC megger | -- |
|
Between all terminals connected together and DIN rail |
100 MΩ min., 500 VDC megger | ||
|
Dielectric strength |
Between logical AND connection terminals, and power supply input terminals and other input and output terminals connected together |
500 VAC for 1 min | -- |
|
Between all terminals connected together and DIN rail |
1,200 VAC for 1 min | ||
|
Between different poles of outputs |
-- | 1,200 VAC for 1 min | |
|
Between safety relay outputs connected together and other terminals connected together |
2,200 VAC for 1 min | ||
| Vibration resistance | Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | ||
|
Mechanical shock resistance |
Destruction | 300 m/s2 | |
| Malfunction | 100 m/s2 | ||
| Durability | Electrical | -- | 100,000 cycles min. (rated load, switching frequency: 1,800 cycles/hour) |
| Mechanical | -- | 5,000,000 cycles min. (switching frequency: 7,200 cycles/hour) |
|
| Ambient temperature | -10 to 55°C (no icing or condensation) | ||
| Ambient humidity | 25 % to 85 % | ||
| Terminal tightening torque *7 | 0.6 Nm | ||
| Weight | Approx. 240 g | Approx. 165 g | |
*6. The value of the operating time and response time of the connected Low-speed Monitoring Unit is not included.
*7. For the G9SX-[]-RT (with screw terminals)
| Model | G9SX-LM224 | G9SX-EX401-[] |
|---|---|---|
| Number of Units connected per logical AND output | 4 units max. | -- |
| Total number of Units connected by logical AND * | 20 units max. | -- |
| Number of Units connected in series by logical AND | 5 units max. | -- |
| Max. number of Expansion Units connected | -- | 5 units max. |
| Maximum cable length for logical AND input | 100 m max. | -- |
* The number of G9SX-EX401-[] Expansion Units not included.