FAQ No. FAQ00846
Question
With
61F-G1 Floatless Level Controller, the
water level of a water supply is above the E2' height, but the pump does
not operate. What is the cause of the problem and how can it be corrected?
Answer
The following items may be the cause, so check these.
Likely Causes
Countermeasures
1. Momentarily short the E1' and E3 terminals of the 61F-G1 Controller to
operate (self-hold) the U1 Relay Unit.
2. When the U1 Relay Unit will not operate (self-hold), replace the U1
Relay Unit. Also, check whether there is a damaged cable between the 61F
Controller and electrode, and check whether the E2' electrode is coated
with tarnish or oil.
3. As an emergency measure, operation can be forced by shorting the E1'
and E3 terminals on the 61F-G1 Controller, however, idling cannot be
prevented in this case.